69
16.4. Error Codes Table
Abnormality / Protection control
Abnormality Judgement
Primary location to verify
Diagnosis display
H00
No abnormality detected
—
—
H12
Indoor/Outdoor capacity unmatched
90s after power supply
• Indoor/outdoor connection wire
• Indoor/outdoor PCB
• Specification and combination table in
catalogue
H15
Outdoor compressor temperature sensor
abnormality
Continue for 5 sec.
• Compressor temperature sensor
(defective or disconnected)
H23
Indoor refrigerant liquid temperature
sensor abnormality
Continue for 5 sec.
• Refrigerant liquid temperature sensor
(defective or disconnected)
H42
Compressor low pressure abnormality
—
• Outdoor pipe temperature sensor
• Clogged expansion valve or strainer
• Insufficient refrigerant
• Outdoor PCB
• Compressor
H62
Water flow switch abnormality
Continue for 1 min.
• Water flow switch
H64
Refrigerant high pressure abnormality
Continue for 5 sec.
• Outdoor high pressure sensor
(defective or disconnected)
H70
Back-up heater OLP abnormality
Continue for 60 sec.
• Back-up heater OLP
(Disconnection or activated)
H72
Tank sensor abnormal
Continue for 5 sec.
• Tank sensor
H76
Indoor - control panel communication
abnormality
—
• Indoor - control panel
(defective or disconnected)
H90
Indoor / outdoor abnormal
communication
> 1 min after starting operation
• Internal / external cable connections
• Indoor / Outdoor PCB
H91
Tank heater OLP abnormality
Continue for 60 sec.
• Tank heater OLP
(Disconnection or activated)
H95
Indoor/Outdoor wrong connection
—
• Indoor/Outdoor supply voltage
H98
Outdoor high pressure overload
protection
—
• Outdoor high pressure sensor
• Water pump or water leakage
• Clogged expansion valve or strainer
• Excess refrigerant
• Outdoor PCB
H99
Indoor heat exchanger freeze prevention
—
• Indoor heat exchanger
• Refrigerant shortage
F12
Pressure switch activate
4 times occurrence within 20
minutes
• Pressure switch
F14
Outdoor compressor abnormal revolution
4 times occurrence within 20
minutes
• Outdoor compressor
F15
Outdoor fan motor lock abnormality
2 times occurrence within 30
minutes
• Outdoor PCB
• Outdoor fan motor
F16
Total running current protection
3 times occurrence within 20
minutes
• Excess refrigerant
• Outdoor PCB
F20
Outdoor compressor overheating
protection
4 times occurrence within 30
minutes
• Compressor tank temperature sensor
• Clogged expansion valve or strainer
• Insufficient refrigerant
• Outdoor PCB
• Compressor
F22
IPM (power transistor) overheating
protection
3 times occurrence within 30
minutes
• Improper heat exchange
• IPM (Power transistor)
F23
Outdoor Direct Current (DC) peak
detection
7 times occurrence
continuously
• Outdoor PCB
• Compressor
F24
Refrigeration cycle abnormality
2 times occurrence within 20
minutes
• Insufficient refrigerant
• Outdoor PCB
• Compressor low compression
F25
Cooling / Heating cycle changeover
abnormality
4 times occurrence within 30
minutes
• 4-way valve
• V-coil
F27
Pressure switch abnormality
Continue for 1 min.
• Pressure switch
F36
Outdoor air temperature sensor
abnormality
Continue for 5 sec.
• Outdoor air temperature sensor
(defective or disconnected)
F37
Indoor water inlet temperature sensor
abnormality
Continue for 5 sec.
• Water inlet temperature sensor
(defective or disconnected)
F40
Outdoor discharge pipe temperature
sensor abnormality
Continue for 5 sec.
• Outdoor discharge pipe temperature
sensor (defective or disconnected)
Содержание WH-SXF12D6E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up The Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Страница 21: ...21 7 2 WH UX12DE5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXF09D3E5 ...
Страница 23: ...23 8 1 2 WH SXF12D6E5 ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXF09D3E5 ...
Страница 26: ...26 9 1 2 WH SXF12D6E5 ...
Страница 27: ...27 9 2 Outdoor Unit ...
Страница 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Страница 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 48: ...48 Heat Tank Mode Heating priority not set Under Solar Priority Set Condition ...
Страница 49: ...49 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 106: ...106 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UX09DE5 WH UX12DE5 ...
Страница 117: ...117 ...