70
F41
PFC control
4 times occurrence within 10
minutes
• Voltage at PFC
F42
Outdoor heat exchanger temperature
sensor abnormality
Continue for 5 sec.
• Outdoor heat exchanger temperature
sensor (defective or disconnected)
F43
Outdoor defrost sensor abnormality
Continue for 5 sec.
• Outdoor defrost sensor (defective or
disconnected)
F45
Indoor water outlet temperature sensor
abnormality
Continue for 5 sec.
• Water outlet temperature sensor
(defective or disconnected)
F46
Outdoor Current Transformer open
circuit
—
• Insufficient refrigerant
• Outdoor PCB
• Compressor low
F48
Outdoor EVA outlet temperature sensor
abnormality
Continue for 5 sec.
• Outdoor EVA outlet temperature sensor
(defective or disconnected)
F49
Outdoor bypass outlet temperature
sensor abnormality
Continue for 5 sec.
• Outdoor bypass outlet temperature
sensor (defective or disconnected)
F95
Cooling high pressure overload
protection
—
• Outdoor high pressure sensor
• Water pump or water leakage
• Clogged expansion valve or strainer
• Excess refrigerant
• Outdoor PCB
Abnormality / Protection control
Abnormality Judgement
Primary location to verify
Diagnosis display
Содержание WH-SXF12D6E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up The Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Страница 21: ...21 7 2 WH UX12DE5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXF09D3E5 ...
Страница 23: ...23 8 1 2 WH SXF12D6E5 ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXF09D3E5 ...
Страница 26: ...26 9 1 2 WH SXF12D6E5 ...
Страница 27: ...27 9 2 Outdoor Unit ...
Страница 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Страница 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 48: ...48 Heat Tank Mode Heating priority not set Under Solar Priority Set Condition ...
Страница 49: ...49 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 106: ...106 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UX09DE5 WH UX12DE5 ...
Страница 117: ...117 ...