14 Servicing Mode
14.1. Test Run
1. Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation instruction.
2. Set ON to the indoor unit and RCCB/ELCB. Then, for control panel’s operation please refers to air-to-water heatpump’s
operation instruction.
3. For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.2 MPa.
If necessary, adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water pump
speed cannot solve the problem, contact your local authorized dealer.
14.2. Proper Pump Down Procedure
1. Make sure the OFF/ON control panel LED is OFF (no operation).
2. Press the “PUMPDW” switch on control panel to begin PUMP DOWN mode. Operate the system in PUMP DOWN mode for
10 ~ 15 minutes.
3. After 10-15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10 C)), fully close 2 way valve.
4. After 3 minutes, fully close 3 way valve.
5. Press the “OFF/ON” switch on control panel to stop PUMP DOWN mode.
6. Remove the refrigerant piping.
14.3. How To Adjust Water Flow Rate
• Before adjust the water flow rate, make sure that the total water volume in the installation is 50 litres minimum.
• The water flow rate can be adjusted with select the water pump speed on the water pump. The default setting is moderate speed
(II). However, please ensure the minimum flow rate cannot be less than 18L/min. Adjust it to high speed (III) and slow speed (I) if
necessary (e.g. reduce the noise of running water).
• Below graph shown the external static pressure (kPa) versus water flow rate (L/min).
• Flow rate characteristic of indoor unit is as per above mentioned.
14.4. Expansion Vessel Pre Pressure Checking
• Expansion Vessel with 10L air capacity and initial pressure of 1 bar is installed in this indoor unit.
• Total amount of water in system should be below 200L.
(Note: This amount of water is not include the tank unit volume)
• If total amount of water is over 200L, please add expansion vessel.
• Please keep the installation height difference of system water circuit within 7m.
(Inner volume of same indoor unit is about 5L)
Содержание WH-SXF12D6E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up The Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Страница 21: ...21 7 2 WH UX12DE5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXF09D3E5 ...
Страница 23: ...23 8 1 2 WH SXF12D6E5 ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXF09D3E5 ...
Страница 26: ...26 9 1 2 WH SXF12D6E5 ...
Страница 27: ...27 9 2 Outdoor Unit ...
Страница 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Страница 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 48: ...48 Heat Tank Mode Heating priority not set Under Solar Priority Set Condition ...
Страница 49: ...49 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 106: ...106 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UX09DE5 WH UX12DE5 ...
Страница 117: ...117 ...