3. When quiet request OFF time by weekly timer
When any of above mentioned condition is achieved, this control is cancelled.
12.14. Solar operation (Optional)
12.14.1. Solar operation
1. Control according to preset whether Solar Priority is set or not.
2. When tank connection is NOT set at SETTING mode, Solar operation is disabled.
3. When Pump A (from Solar pump station) is detected On through connection Y3 and Y4, then the Solar pump 3 Way Valve is
requested ON (Refer to figure below).
12.14.2. Solar operation control
When solar priority is SET
1. Operation condition:
a. Solar pump operates if all of the following conditions are fulfilled:-
• Power On. (regardless operation ON or OFF).
• There is operation request from Solar pump station.
• Tank hot water temp is below solar on upper limit temp [EEPROM 1 : 70] C.
2. Stop condition:
a. Solar pump stops operating when:-
• No power supply to unit
OR
• There is
NO
operation request from Solar pump station
OR
• Tank hot water temp is above solar off upper limit temp [EEPROM 2 : 77] C.
* heat pump OFF OR operate to room side when solar pump operate during solar priority set.
* booster heater OFF when solar pump operate during solar priority set.
When solar priority is NOT SET
1. Operation condition:
a. Solar pump operates if all of the following conditions are fulfilled:-
• Power On. (regardless operation ON or OFF).
• There is operation request from Solar pump station.
• Tank hot water temp is below solar on upper limit temp [EEPROM 1 : 70] C.
• Heat pump thermo Off in tank mode OR Heat pump operate to room side (During Operation ON and tank mode selected).
2. Stop condition:
a. Solar pump stops operating when:-
• No power supply to unit
OR
• There is
NO
operation request from Solar pump station
OR
• Tank hot water temp is above solar off upper limit temp [EEPROM 2 : 77] C.
• Heat pump thermo ON and operate to tank side. (During Operation ON and tank mode selected).
Содержание WH-SXF12D6E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up The Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Страница 21: ...21 7 2 WH UX12DE5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXF09D3E5 ...
Страница 23: ...23 8 1 2 WH SXF12D6E5 ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXF09D3E5 ...
Страница 26: ...26 9 1 2 WH SXF12D6E5 ...
Страница 27: ...27 9 2 Outdoor Unit ...
Страница 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Страница 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 48: ...48 Heat Tank Mode Heating priority not set Under Solar Priority Set Condition ...
Страница 49: ...49 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 106: ...106 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UX09DE5 WH UX12DE5 ...
Страница 117: ...117 ...