15 Maintenance Guide
In order to ensure optimal performance of the unit, checks and inspections on the unit and the field wiring must be carried out
regularly. Please request a licensed technician for carry out maintenance job.
Before carried out any maintenance or repair work, and removing the front plate of heat exchanger unit, always switch off all power
supply (i.e. indoor unit power supply, heater power supply and sanitary tank power supply).
Below checks must be carried out at least once a year.
1. Water pressure
Water pressure should not lower than 0.05 MPa (with inspects the pressure gauge). If necessary add tap water into boiler
tank. Refer to boiler tank installation instruction for details on how to add water.
2. Pressure relief valve
• Check for correction operation of pressure relief valve by turn up the lever to become horizontal. (Refer to figure below)
• If you do not hear a clacking sound (due to water drainage), contact your local authorized dealer.
• Turn down the lever after checking finish.
• In case the water keeps drained out from the unit, switch off the system, and then contact your local authorized dealer.
3. Indoor unit control board area
Thorough visual inspection of the control board and look for defects, i.e. loose connection, melting of wire insulator and etc.
4. RCCB/ELCB
Ensure the RCCB/ELCB set to “ON” condition before check RCCB/ELCB.
Turn on the power supply to the indoor unit.
This testing could only be done when power is supplied to the indoor unit.
• Push the “TEST” button on the RCCB/ELCB. The lever would turn down and indicate “0” and indicate green colour if it
functions normal.
• Contact authorized dealer if the RCCB/ELCB malfunction.
• Turn off the power supply to the indoor unit.
• If RCCB/ELCB functions normal, set the lever to “ON” again after testing finish.
5. How to release the trapped air in water circuit
• Turn up the lever to become horizontal. (Refer to figure “Pressure relief valve”). The trapped air will be drained out together
with water. After few seconds, turn down the lever to stop the water drainage.
• Repeat it until the bubbling sound disappear.
6. Reset overload protector
Overload Protector serves the safety purpose to prevent the water over heating. When the Overload Protector trip at high
water temperature, take below steps to reset it.
a. Take out OLP Cover.
Becareful not to touch parts other than RCCB/ELCB test button when the power is supplied to Indoor Unit. Else, electrical shock
may happen.
Содержание WH-SXF12D6E5
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 ...
Страница 13: ...13 4 1 2 Weekly Timer Setting ...
Страница 14: ...14 4 1 3 Setting Up The Special Functions ...
Страница 15: ...15 4 1 4 Main Components 4 2 Outdoor Unit ...
Страница 16: ...16 5 Dimensions 5 1 Indoor Unit ...
Страница 17: ...17 5 2 Outdoor Unit ...
Страница 19: ...19 ...
Страница 20: ...20 7 Block Diagram 7 1 WH UX09DE5 ...
Страница 21: ...21 7 2 WH UX12DE5 ...
Страница 22: ...22 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SXF09D3E5 ...
Страница 23: ...23 8 1 2 WH SXF12D6E5 ...
Страница 24: ...24 8 2 Outdoor Unit ...
Страница 25: ...25 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SXF09D3E5 ...
Страница 26: ...26 9 1 2 WH SXF12D6E5 ...
Страница 27: ...27 9 2 Outdoor Unit ...
Страница 28: ...28 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 29: ...29 10 1 2 Solar Printed Circuit Board Optional ...
Страница 30: ...30 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 31: ...31 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 48: ...48 Heat Tank Mode Heating priority not set Under Solar Priority Set Condition ...
Страница 49: ...49 Heat Tank Mode Heating priority not set Under Solar Priority Not Set Condition ...
Страница 57: ...57 ...
Страница 58: ...58 ...
Страница 105: ...105 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 106: ...106 17 5 To Remove RCCB ELCB 17 6 To Remove Transformer and Electronic Controller Board ...
Страница 116: ...116 19 2 WH UX09DE5 WH UX12DE5 ...
Страница 117: ...117 ...