45
11.5 Checking and Test Run Procedures
WARNING
Be sure to switch off all the power supply before performing each of the below action.
11.5.1 Disposal of Mono Bloc Unit Drain Water
When a Drain elbow
1
is used, please ensure to follow below:
o
The unit should be placed on a stand which is taller than 50mm.
o
Cover the 8 holes (ø20mm) with Rubber cap
2
(refer to illustration below)
o
Use a tray (field supply) when necessary to dispose the Mono bloc unit drain water.
If the unit is used in an area where temperature falls below 0°C for 2 or 3 consecutive days, it is recommended
not to use the Drain elbow
1
and Rubber cap
2
, for the drain water freezes and the fan will not rotate.
(1) Remove the 5 mounting screws
as shown in the illustration.
(2) Slide the cabinet front plate
downward to release the pawls.
Then, pull it toward front to
remove it.
Remove The Cabinet Front Plate
(1) Remove the 11 mounting screws
as shown in the illustration.
(2) Lift the cabinet top plate
upward to remove it.
Remove The Cabinet Top Plate
Mounting screws
Mounting
screws
Mounting
screws
8
9
8
9
8
9
Drain elbow
Rubber cap
× 8
2
1
Содержание WH-MHF09G3E5
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ACL PUMP L PUMP N CN SOLAR_B ACL1 3V ACL2 3V ACN 3V ACN ...
Страница 132: ...132 8 25 6 30 68 24 71 13 62 75 10 12 1 3 15 4 2 15 4 20 21 5 71 8 77 7 23 26 14 78 9 11 13 ...
Страница 136: ...136 19 2 Water System 2 45 44 46 34 17 16 4 1 45 47 3 18 36 33 9 35 19 43 ...