80
16. Troubleshooting
Guide
16.1 Refrigeration Cycle System
In order to diagnose malfunctions, make sure that there
are no electrical problems before inspecting the
refrigeration cycle.
Such problems include insufficient insulation, problem
with the power source, malfunction of a compressor and a
fan.
The normal pressure of the refrigeration cycle depends
on various conditions, the standard values for them are
shown in the table on the right.
Value of electric
current during operation
Lower than specified
Higher than specified
Heating Mode
Low
Low
Low
Gas side
pressure
Water leakage or insufficient
water flow rate in the system
●
Measuring electric current
during operation
●
Measuring gas side pressure
Excessive amount
of refrigerant
Inefficient compressor
Insufficient refrigerant
Clogged strainer or
expansion valve
Normal Pressure (Standard)
Gas pressure
MPa (kg/cm
2
G)
Heating Mode
1.4 ~ 1.8 (14 ~ 18)
Condition: • Outdoor temperature 7°C at
heating mode.
• Compressor operates at
rated frequency.
• Water outlet temperature
35°C at heating mode.