16.5.7 Water Flow Switch Abnormality (H62)
Malfunction Decision Conditions:
During operation of heating, the water flow detected by the indoor water flow switch is used to determine water
flow error.
Malfunction Caused:
1 Faulty
water
pump.
2 Water leak in system.
3 Faulty
connector
connection.
4 Faulty water flow switch.
5 Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart).
Troubleshooting:
For safety reason and to prevent component breakdown,
always switch off the power before remove and connect the component.
Check the system water pump.
Is the CN-FLOW connector
connection normal?
Is there any continuity?
Check the system water passage.
Is the water pump working?
Is there any water leakage?
Yes
Yes
Yes
Yes
No
No
No
No
Replace the faulty water
pump.
- Connector poor contact.
- Correct the connection.
- Defect in indoor water flow
switch.
- Replace the indoor water
flow switch.
- Defect in indoor unit PCB
(main).
- Replace the indoor unit PCB
(main).
Fix the system water
leakage.
Check the CN-FLOW connector connection:
- Turn OFF the power
- Check the connector connection
Check the indoor water flow switch:
- Plug out connector from the indoor
unit PCB (main).
- Dismantle the water flow switch.
- Position the water flow switch in
reverse direction (downward).
- Measure the continuity of the
water flow switch.