12.15 External Room Thermostat Control (Optional)
Purpose:
1 Better room temperature control to fulfill different temperature request by external room thermostat.
Recommended external room thermostat:
Maker Characteristic
Siemen (REV200)
Touch panel
Siemen (RAA20)
Analog
Connection of external room thermostat:
Wire Connection and thermo characteristic of Siemen REV200:
Setting
L/L1 (H)
Heat Thermo
L/L2 (C)
Cool Thermo
Set Temp < Actual Temp
Open Circuit OFF Short
Circuit ON
Set Temp > Actual Temp
Short Circuit
ON
Open Circuit
OFF
Wire Connection and thermo characteristic of Siemen RAA20:
Setting
L/Y1
(H) Heat
Thermo L/Y2
(C) Cool
Thermo
Set Temp < Actual Temp
Open Circuit OFF Short
Circuit ON
Set Temp > Actual Temp
Short Circuit
ON
Open Circuit
OFF
Control Content:
External room thermostat control activate only when remote thermostat connection select YES by control panel.
When indoor running heat mode, refer thermo On/Off from heating line feedback. And when indoor running cool
mode, refer thermo On/Off from cooling line feedback.
Heat pump Off immediately when receive thermo off feedback.
Cooling
Heating
Siemen REV200
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
Indoor Unit
9
L (label)
10
11
12
L2 (label)
L1 (label)
9 : Terminal Board No.
Cooling
Heating
Siemen RAA20
Connect only heating line for heating only model. And connect both
heating and cooling line for heat + cool model.
Indoor Unit
9
L (label)
10
11
12
Y2 (label)
Y1 (label)
9 : Terminal Board No.
Содержание WH-MHF09G3E5
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ACL PUMP L PUMP N CN SOLAR_B ACL1 3V ACL2 3V ACN 3V ACN ...
Страница 132: ...132 8 25 6 30 68 24 71 13 62 75 10 12 1 3 15 4 2 15 4 20 21 5 71 8 77 7 23 26 14 78 9 11 13 ...
Страница 136: ...136 19 2 Water System 2 45 44 46 34 17 16 4 1 45 47 3 18 36 33 9 35 19 43 ...