49
DETECT FREQUENCIES [OUTPUT TR], [OUTPUT RY]
(Parameter P27 and P28)
Used to set the frequency to be detected when outputting the frequency detection signal
with the open collector output or relay output.
[Parameter P27 : Open collector output detection frequency setting]
[Parameter P28 : Relay output detection frequency setting]
Data setting range
(Hz)
000 • 0.5 to 250
Setting unit
(Hz)
0.1 (0.5 to 100Hz) 1 (100 to 250Hz)
♦
♦
♦
♦
Relation of output frequency and each output signal
Output frequency
Run signal (OFF)
Frequency detection signal (OFF)
Set frequency (
±
2Hz)
Detection frequency
Parameter P27
Parameter P28
(ON)
(ON)
(OFF)
(OFF)
Arrival signal (OFF)
(OFF)
(OFF)
(ON)
(ON)
JOG FREQUENCY, JOG ACCELERATION TIME, JOG DECELERATION
TIME (Parameter P29, P30 and P31)
Used to set the operating frequency, acceleration/deceleration time when jog operation is
executed.
[Parameter P29: Jog frequency setting]
Data setting range
(Hz)
0.5 to 250
[Parameter P30 : Jog acceleration time setting]
[Parameter P31 : Jog deceleration time setting]
Data setting range
(sec.)
0.04 • 0.1 to 999
Note)
"000" is displayed for 0.04 seconds.
[Jog operation]
·
The operation command select must be set to external control.
(The data for parameter P08 must be set between "2 and 5".)
·
The SW select function must be set to the jog function.
·
If the SW set for the jog function turns ON (closed), the inverter will enter the jog
operation preparation completed state.
·
Carry out jog operation start/stop and forward/reverse with control terminals No. 5 and 6.