37
Out
p
ut
vol
ta
g
e
(%
)
Output frequency
Out
p
ut
vol
ta
g
e
(%
)
Output frequency
Out
p
ut
vol
ta
g
e
(%
)
Output frequency (Hz)
100
0
50 (Hz)
100
0
60 (Hz)
Base frequency (P16)
0
100
Max. output frequency
(P15)
1st ACCELERATION TIME (Parameter P01)
Used to set the time to accelerate to the maximum output
frequency from 0.5Hz.
Data setting range (sec)
0.04 • 0.1 to 999
Setting unit
(sec)
0.1 (0.1 to 100) 1 (100 to 999)
●
The display code for 0.04 sec. is "000".
●
The maximum output frequency is set with parameters P03
and P15.
1st DECELERATION TIME (Parameter P02)
Used to set the time to decelerate from the maximum output
frequency to 0.5Hz.
Data setting range (sec)
0.04 • 0.1 to 999
Setting unit
(sec)
0.1 (0.1 to 100) 1 (100 to 999)
●
The display code for 0.04 sec. is "000".
●
The maximum output frequency is set with parameters P03
and P15.
FREQUENCY RANGE (V/F PATTERN) (Parameter P03)
A frequency range of 50/60Hz or 50 to 250Hz can be set independently from the maximum
output frequency (50 to 250Hz).
Data setting
value
Name Remarks
50 50Hz
mode
60 60Hz
mode
The frequency range is set regardless of the parameter P15 and
P16 settings.
FF Free
mode
The frequency range is set according to the parameter P15 and P16
settings.
The maximum output frequency is set in parameter P15 and the
base frequency is set in parameter P16.
[50Hz mode]
[60Hz mode]
[Free mode]
·
Max. output frequency
·
Max. output frequency
= 50Hz
= 60Hz
·
Base frequency = 50Hz
·
Base frequency = 60Hz
Functional Descriptions (By Parameter )
Out
put
f
requenc
y
(Hz
)
Max. output
frequency
Decelera-
tion time
0.5
Out
put
f
requenc
y
(Hz
)
Max. output
frequency
Accelera-
tion time
0.5