31
Various function data can be changed and set when the operation is stopped.
Note that some functions can be changed during operation. (See page 32.)
●
Setting functions when operation is stopped.
[Setting example: Change the maximum frequency from 50Hz to 60Hz]
[Setting precautions]
1. After the function is set, the inverter will not run unless the MODE button is
pressed and the "operation preparation completed" state is returned to.
2. If the function setting returns to the "operation preparation completed"
state during data changing, while a start input signal is being applied
through external control, an "OP" error will be displayed, causing the
inverter to remain inoperative.
∗
Reset the fault indication using the instructions under "Resetting Fault
Trips" on page 73.
3. The set data will be stored in the memory even after the power supply has
been turned OFF.
Setting and Changing Functions
(Changing the parameter P03 data from "50" to "60")
Press the STOP button to stop the inverter.
Press the SET button to display the parameter P03 data.
(The main display will flicker.)
STOP
Press the
(up) button twice, and change the parameter No. to P03.
Press the MODE button.
Press the MODE button.
Press the MODE button. (Enter the function setting mode.)
(If a password is set, it must be entered at this point. See page 62.)
Press the
(up) button, and change the data display value to "60".
(The main display will flicker.)
Press the SET button to set the data.
Press the MODE button to return to "operation preparation completed."
OPERATION PREPARATION
COMPLETED
The normal stop state will be entered and the
inverter can be run.