20
■
Wiring
4 to 20mA
C
B
A
1
2
3
4
5
6
7
8
9
10 11
COM NC NO
+
-
VR
0 to 5V
0 to 10V
Start/st
o
p
Forw
ard/rev
e
rs
e SW1
SW3
SW2
-
+
Analog
output
(0 to 5V)
E
C
Open collector
output
Relay output
+
-
200
Ω
♦
Terminal specifications: "Screw size: M3 (minus screw)"
"Tightening torque: 0.5 to 0.6N·m"
♦
Frequency setting potentiometer (VR) specifications: "10k
Ω
, 1/4W or more
potentiometer"
♦
Relay output contact specifications: 1c no-voltage contact, 250VAC, 0.5A
(resistance load)
♦
Open collector output specifications: Maximum rating 50VDC, 50mA
Note 1)
When using a 4 to 20mA signal for the frequency setting, always
connect a 200
Ω
, 1/4W resistor. (The inverter could be damaged if
the resistor is not connected.)
Note 2)
Always read each function explanation for the parameters related to
each terminal before starting use.
Terminal
No.
Terminal function
Related parameter No.
1
Frequency setting potentiometer connection terminal (+5V)
P09
2
Frequency setting analog signal input terminal
P09
3
Common terminal for 1 , 2 , 4 to 9 signals
4
Multi-function analog signal output terminal (0 to 5V/PWM)
P58, P59
5
Start/stop, forward run signal input terminal
P08
6
Forward/reverse, reverse run signal input terminal
P08
7
Multi-function control signal SW1 input terminal
P19, P20, P21
8
Multi-function control signal SW2 input terminal
Frequency setting signal changeover input terminal
P19 to P21
P22 to P24
9
Multi-function control signal SW3 input terminal
PWM signal input terminal
P19 to P21
P22 to P24
10
Open collector output terminal (C: collector)
P25
11
Open collector output terminal (E: emitter)
P25
A
Relay contact output terminal (NO: at factory setting)
P26
B
Relay contact output terminal (NC: at factory setting)
P26
C
Relay contact output terminal (COM)
P26
Control Circuit Wiring
∗
Only basic insulation (Protection against Electric Shock Class
I
, Overvoltage
category
II
, Pollution degree 2) is provided on the control circuit terminals.
The supplementary insulation must be provided on the final product to comply
with CE Marking requirements.