55
RIDE-THROUGH RESTART (Parameter P49)
CAUTION
:
●
Depending on the ride-through restart function settings, the motor may restart suddenly
after the power is restored.
(Ensure personal safety before restarting.)
Failure to do so could lead to injury.
Used to select the restart mode after an instantaneous power failure occurs, according to the
load conditions and system. A wait timer function is built-in.
Inverter operation in regard to instantaneous power failure time
Data
setting
value
Min. 15ms or
less (Note 1)
Exceeding min. 15ms
(Note 1)
Min. 100ms or less
(Note 2)
Exceeding min. 100ms
(Note 2)
0
•
The LU trips, and the inverter operates according to the start mode settings.
•
"LU" will be displayed, and a fault warning signal will be output.
1
•
Restarts from 0Hz after the wait time has elapsed.
•
"LU" will be displayed, but a fault warning signal
will not be output.
2
Operation
continues
•
After the wait time has elapsed, the inverter
restarts at the frequency applied before the
ride-through restart occurred.
•
"LU" will be displayed, but a fault warning signal
will not be output.
Operation takes place
according to the details
set in the start mode.
Note 1)
This is the min. time for operation at the rated output current.
(This time may be longer depending on the model.)
Note 2)
This is the min. time. (This time may be longer if the rated capacity is larger.)
Even if the power failure time is relatively long (approx. 1 min.), the inverter may
restart after the power is restored. Wait at least four min. (wait time + 2 min.) after
the power is restored before handling the inverter, motor or load facility.
Note 3)
The wait time can be set between 0.1 to 100 sec. with parameter P50.
[When voltage drop time is more than 15ms but less than 100ms.]
Voltage drop time
LU trip
Power
supply
Output
frequency
Output
frequency
Output
frequency
LU trip
LU trip
LU level
Wait time
(Parameter P50)
Current limit function
Operates according to the
start mode setting details
0
0
0
0
• Data setting value "0"
(No restart)
• Data setting value "1"
(0Hz restart)
• Data setting value "2"
(Pickup restart)