![Panasonic VF0 Series Скачать руководство пользователя страница 60](http://html.mh-extra.com/html/panasonic/vf0-series/vf0-series_instruction-manual_269848060.webp)
59
ANALOG/PWM OUTPUT FUNCTION SELECT (Parameter P58)
The "0 to 5V voltage signal" output from the control circuit terminal No. 4 and the functions
of the "output status signal (PWM)" output from terminals No. 10-11 can be set.
Data setting value
Details of function
0
Signal proportional to output frequency is output
1
Signal proportional to output current is output
♦
Relation of 0 to 5V voltage signal and output frequency/output current
[For proportion to output frequency]
[For proportion to output current]
V
ol
tage
s
ignal
ou
tput
0
Output frequency
5
Maximum output
frequency
V
ol
tage s
ignal
out
put
(V)
0
5
150% of rated
output current
Output current
(V)
♦
Relation of PWM output signal and output frequency/output current
[For proportion to output frequency]
[For proportion to output current]
Dut
y
0
Output frequency
75
Maximum output
frequency
Dut
y
(%)
0
75
150% of rated
output current
Output current
(%)
Note 1)
The parameter P25 (output TR function selection) data must be "7" for the "PWM
output" to be attained from terminals No. 10-11.
Note 2)
The PWM output signal cycle is "1ms".
[Handling of 0 to 5V voltage output, and output status signal (PWM)]
1) The output signal is not intended for precise measurement. Use this only as a guide
value. (Use a separate measuring instrument when precise values are required.)
2) The signal proportional to the output current may output a relatively large value at
approx. 40% or less of the rated current.
(For example, even if there is no output current, a certain signal level may be output.
Note that when the inverter is stopped, the "0 level" will be output.)
ANALOG/PWM OUTPUT COMPENSATION (Parameter P59)
The "0 to 5V voltage signal" and "output status signal (PWM)" output can be compensated.
Data setting range (%)
75 to 125
Setting unit (%)
1
<<Adjustment range (Full scale value)>>
1) Voltage signal : 3.75 to 5 to 6.25 (V)
2) PWM signal
: 56.3 to 75 to 93.8 (%)