68
z
Nine types of functions can be selected for the multi-function input terminals
No. 7, 8, 9 (SW1, SW2, SW3). Refer to the following explanation and use
these functions effectively.
1. Multi-speed SW function (Parameters: P19, P20, P21/Data setting value: 0)
Eight types of frequencies can be selected, changed and controlled with the three
switch signals SW1, 2 and 3.
(Speed 1: Parameter P09 setting signal, Speeds 2 to 8: Parameter P32 to P38 set
frequency)
<<Example>>
When Speed 1 is set to 50Hz, and speeds 2 to 8 are set to factory
setting
SW1
SW2
SW3
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(1)
(1)
Ou
tp
ut
f
requ
en
cy
Speed 8
(
45Hz
)
Speed 7
(
35Hz
)
Speed 6
(
25Hz
)
Speed 5
(
15Hz
)
Speed 4
(
40Hz
)
Speed 2
(
20Hz
)
Speed 3
(
30Hz
)
Speed 1
(
50Hz
)
ON
ON
ON
ON
ON
ON
ON
(Terminal No. 7)
(Terminal No.
8)
(Terminal No.
9)
∗
When using one switch input for this function, there will be two speeds, and when
two switches are used, there will be four speeds. (Example: When only SW1 is used,
the speeds will change between speed 1 and speed 2. When SW1 and SW2 are
used, the speeds will change between speeds 1 and 4.)
∗
If "000" is set for the speeds 2 to 8 frequency (parameters P32 to P38), the inverter
will stop (0V stop) when that multi-speed frequency is selected.
2. Reset input function (Parameters: P19, P20, P21/Data setting value: 1)
This function resets the fault stop state from an external device when the inverter trips
(stops) with a fault.
Run signal
Reset signal
O
u
tput fre
que
ncy
Fault trip
Reset completed
ON
Operation according to power loss start mode
(parameter P48) setting
·
P48 = 0 : Immediately starts
·
P48 = 1 : OP stop (factory setting data)
·
P48 = 2 : Start after wait time
·
P48 = 3 : OP stop
ON
∗
When starting/stopping with the operation
panel, operation is restarted with the
panel after resetting. The operation will
not resume just by resetting.
∗
The fault trip can also be reset by turning
the run signal OFF (stopping).
Supplementary Explanation for
Multi-function Terminal Input