PWM CONTROL FUNCTION SELECT, PWM SIGNAL AVERAGING and
PWM SIGNAL CYCLE (Parameters P22, 23, 24)
With this VF0, the operating frequency can be controlled with the PWM signals output from
the PLC, etc.
(Note that the tolerable PWM signal cycle is between 0.9ms and 1100ms.)
[Parameter P22: PWM control function select]
Data setting value
Details
0
PWM control function
selection disabled
1
PWM control function
selection enabled
♦
♦
♦
♦
Explanation of control circuit terminal connection and functions
1) Terminal No. 8: Frequency signal changeover input terminal
ON : Signal set with parameter P09
OFF : PWM signal
2) Terminal No. 9: PWM signal input terminal
Input with an open collector signal having a capability of the
maximum rated voltage and current: 50VDC, 50mA or more.
♦
♦
♦
♦
Relation of PWM signal and frequency command value
OFF (Tr)
ON (Tr)
OFF (Tr)
ON (Tr)
Voltage waveform across
terminals No. 9 and 3
Frequency command value (Hz) =
ON time
PWM cycle
× maximum output frequency (Hz)
PWM cycle
PWM cycle
∗
The maximum output frequency will be "50Hz" when parameter P03 is set to "50", "60Hz"
when set to "60", and "parameter P15 value" when "FF" is set.
Note)
If the PWM control function
is
selected, the SW2 (terminal
No. 8) and SW3 (terminal No.
9) functions will be forcibly
changed to PWM control
dedicated functions.
8
9
3
PWM signal
SW2
Tr