15
[Precautions for installation of
brake resistor (option)]
·
Wait at least 5 minutes after turning
the power OFF before connecting the
resistor. (There is a risk of electric
shock.)
·
Always securely connect the resistor
to the metal plate with metal screws,
etc. (There is a risk of fires.)
·
Install the resistor at a position
separated at least 5cm from the
inverter edges and 10cm or more from
the top. (Resistor cannot be installed
at the bottom.)
·
Note that the resistor will become very hot.
(1) Opening the terminal cover
Lightly press up the center bottom
edge of the terminal cover.
(2) Closing the terminal cover
Lightly press down on the center top
edge of the terminal cover.
Note)
After closing the terminal cover,
confirm that it is securely closed.
(1)
(1)
(2)
Explanation of inside of terminal cover
Opening and closing the terminal cover
Note)
This explanatory drawing shows the
state with the terminal cover removed.
During normal use, do not remove the
terminal cover.
Main circuit terminal
(signal input/output: 1-11)
Control circuit terminal
(relay output: A, B, C)
R S T
U V W
(Main circuit terminal block layout)
Power supply
Motor
DB+
DB
-
Brake resistor connection terminal
Mounting holes
Control circuit terminal
Ground terminal
10cm or more
Brake resistor
5cm or more 5cm or more