6-36. Placing the Unit Inside the Ceiling
This unit is equipped with the drain pump. Check a tape
measure or carpenter’s level.
Before installing the ceiling panel, complete the work of
drain pipe and refrigerant pipe installation.
(1) When placing the unit inside the ceiling, determine the
pitch of the suspension bolts using the supplied full-scale
installation diagram. (Fig. 1-122)
Tubing and wiring must be laid inside the ceiling when
suspending the unit. If the ceiling is already constructed, lay
the tubing and wiring into position for connection to the unit
before placing the unit inside the ceiling.
(2) The length of suspension bolts must be appropriate for a
distance between the bottom of the bolt and the bottom of the
unit of more than 45/64” (18 mm) as shown in Fig. 1-122.
(3) Thread the 3 hexagonal nuts and 2 washers (field supply)
onto each of the 4 suspension bolts as shown in Fig. 1-123.
Use 1 nut and 1 washer for the upper side, and 2 nuts and 1
washer for the lower side, so that the unit will not fall off the
suspension lugs.
(4) Adjust so that the distance between the unit and the ceiling
bottom is 15/32” (12 mm) ~ 43/64” (17 mm). Tighten the nuts
on the upper side and lower side of the suspension lug.
(5) Remove the protective polyethylene used to protect the fan
parts during transport.
(6) Check with a tape measure or carpenter’s level.
Fig. 1-123
Nuts and washers
(use for upper and lower)
Double nut
15/32” (12 mm) ~ 43/64” (17 mm)
Notch
Suspension lug
Suspension bolt
6-37. How to Process Tubing
Refer to the section “4-4. HOW TO PROCESS TUBING” on page 1-112.
Fig. 1-122
Ov
er
45/64”
(18 mm)
15/32”
(12 mm) ~
43/64”
(17 mm)
Air
conditioner
Ceiling
Screw for
attaching paper
(4 points)
Full-scale
installation diagram
Open the ceiling
as large as this
paper outline
Air
conditioner
Over 45/64”
(18 mm)
Full-scale
installation
diagram
Full-scale installation diagram
Ceiling
00_271724_Eng.indb 8
2015-8-26 14:43:52
A
B
1 ft. (300 mm) or less
Indoor unit
Indoor unit
Bend angle 90° prohibited
Bend angle less than 45°
Trap prohibited
Indoor unit
Ceiling surface
Air bleeder prohibited
Separation of support bracket = 4.92 ft. (1.5 m) ~ 6.56 ft. (2 m)
Trap prohibited
Upward gradient
prohibited
* Length of supplied drain pipe = 9-27/32” (250 mm)
Downward gradient = 1/100 or more
A : 2.79 ft. (850 mm) or lower
B : 2.2 ft. (670 mm) or lower
(as short as possible)
Fig. 1-124
Fig. 1-125
Fig. 1-126
Fig. 1-127
Fig. 1-128
6-38. Installing the Drain Pipe
1. Before Performing the Installation Drain Piping
(1) Limitations of Raising the Drain Pipe Connection
CAUTION
The drain pipe can be raised to a maximum height of
2.79 ft. (850 mm) from the bottom surface of the ceiling.
Do not attempt to raise it higher than 2.79 ft. (850 mm).
Doing so will result in water leakage. (Fig. 1-124)
(2) Limitations of Drain Pipe Connection
CAUTION
Do not install the drain pipe with an upward gradient from the
drain port connection. This will cause the drain water to flow
backward and leak when the unit is not operating. (Fig. 1-125)
Do not install an air bleeder as this may cause water to spray
from the drain pipe outlet. (Fig. 1-125)
Do not provide U-trap or bell-shaped trap in the middle of the
drain pipe. Doing so will cause abnormal sound.
(Fig. 1-125)
Make sure the drain pipe has a downward gradient (1/100 or
more; downward from drain port connection).
(Fig. 1-126)
(3) Limitations of Drain Hose Connection
CAUTION
Do not bend the supplied drain hose 90° or more.
Bend it less than 45°. (Fig. 1-127)
Do not make a trap in the middle of the supplied drain hose.
Doing so will cause abnormal sound. (Fig. 1-128)
1
SM830203-04.indb 150
15/10/16 10:45:05
Содержание U-26PE1U6
Страница 8: ...vii MEMO...
Страница 76: ...1 68 1 Specifications 1 4 Dimensional Data Outdoor Unit U 26PE1U6 U 26PS1U6 U 36PE1U6 U 36PS1U6 1...
Страница 77: ...1 69 1 Specifications 1 4 Dimensional Data Outdoor Unit U 42PE1U6 U 42PS1U6 1...
Страница 218: ...2 12 MEMO...
Страница 219: ...3 1 3 2 Indoor Units 3 2 Outdoor Units 3 14 3 ELECTRICAL DATA 3 1 3...
Страница 220: ...3 2 3 Electrical data 3 1 Indoor Units Concealed Duct Type S 26PF2U6 S 36PF2U6 3...
Страница 221: ...3 3 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 222: ...3 4 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 223: ...3 5 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 224: ...3 6 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 225: ...3 7 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 226: ...3 8 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 227: ...3 9 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 228: ...3 10 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 230: ...3 12 3 Electrical data Wall Mounted Type S 26PK2U6 3...
Страница 232: ...3 14 3 Electrical data 3 2 Outdoor Units U 26PE1U6 3...
Страница 233: ...3 15 3 Electrical data U 26PE1U6 3...
Страница 234: ...3 16 3 Electrical data U 26PS1U6 3...
Страница 235: ...3 17 3 Electrical data U 26PS1U6 3...
Страница 236: ...3 18 3 Electrical data U 36PE1U6 3...
Страница 237: ...3 19 3 Electrical data U 36PE1U6 3...
Страница 238: ...3 20 3 Electrical data U 36PS1U6 3...
Страница 239: ...3 21 3 Electrical data U 36PS1U6 3...
Страница 240: ...3 22 3 Electrical data U 42PE1U6 3...
Страница 241: ...3 23 3 Electrical data U 42PE1U6 3...
Страница 242: ...3 24 3 Electrical data U 42PS1U6 3...
Страница 243: ...3 25 3 Electrical data U 42PS1U6 3...
Страница 244: ...MEMO 3 26...
Страница 284: ...5 24 MEMO...
Страница 297: ...201510...