1. Specifications
Push until they hit without space.
2. Installing the Drain Hose
CAUTION
Do not apply force to the drain port when connecting the
drain hose. Install and fix it near the indoor unit as close as
possible.
Do not use adhesive when connecting the drain port pipe
and the drain hose.
(1) How to Install the Drain Hose
1) First insert the supplied hose band into the drain port pipe.
Then make sure the head of the screw is facing toward a
technical engineer when placing the screw of the hose band
at an upward angle.
2) Insert the soft PVC socket of the supplied drain hose to the
drain port pipe. Do not use adhesive when connecting the
drain hose to the drain port pipe.
Insert it until the tip of the drain hose contacts the circular
projection rib of the drain port pipe.
3) Move the hose band so that the center position of the hose
band can be placed approx. 1-3/16” (30 mm) away from the
external plate of the indoor unit. (Fig. 1-129)
4) Screw the drain hose tightly facing the screw of the hose
band upward. (Torque: 22 - 30 lbf·inch (2.5 N·m - 3.4 N·m))
(If the screw is tightened beneath the drain hose, the
troubles will be generated.) Pay attention not to make hose
band overlap the circular projection rib and the sealed
circulation projection of the drain port hose.
5) Move the drain socket showing in the direction of the arrow
toward the drain hose and connect with the adhesive
(approx. 0.07 oz (2 )).
6) Then connect the hard PVC pipe (field supply) on the
opposite side of the drain socket.
Apply the adhesive (approx. 0.07 oz (2 )) between the two
parts.
After connection, remove sticky adhesive left over the
surface.
Fig. 1-129
* After checking the drainage, wrap the supplied packing and drain hose insulator around the hose.
Approx. 13/64” (5mm)
Approx. 1-3/16” (30mm)
Drain insulator (supplied)
Drain insulator
(field supply)
Packing (supplied)
Do not make hose band overlap the circular
projection rib and the sealed circulation
projection of the drain port hose. (Torque: 22 - 30
lbf·inch (2.5 N·m - 3.4 N·m))
Indoor unit
Drain port
(Drainage check section on
drain port, transparent)
Circular
projection rib
Hose band (supplied)
Drain socket (supplied)
Adhere with PVC adhesive.
Do not use adhesive here.
* Drain port may possibly be damaged if
PVC adhesive is used.
Hard PVC pipe
(O.D. 1-5/16” (O.D. 33.4 mm))
(field supply)
Drain hose
(supplied)
Sealed circulation
projection rib
Soft side
Hard side
25/32” (20 mm)
or more
Move the drain socket showing in the direction of the arrow toward
the drain hose and connect with the adhesive (approx. 0.07 oz (2 ).
Then connect the hard PVC pipe (field supply) on the opposite side
of the drain socket.
Apply the adhesive (approx. 0.07 oz (2 ) between the two parts.
After connection, remove sticky adhesive left over the surface.
00_271724_Eng.indb 10
2015-8-26 14:43:53
6-39. Checking the Drainage
Be careful because the fan will start when you short the pin on the indoor control board.
After wiring (refer to “1-12.
ELECTRICAL WIRING”.) and drain piping are completed, use the following procedure to check that the water
will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
(1) Connect power to the power terminal board (L1, L2 terminals) inside the electrical component box.
(2) Slowly pour about 0.3 gal (1,200 cc) of water into the drain pan to check drainage. (Fig. 1-130)
(3) Short the check pin (CHK) on the indoor control board and operate the drain pump. Check the water flow through the transparent
dr
After installation of indoor and outdoor units, panels and electrical wiring, check the following items.
ain pipe and see if there is any leakage.
(4) When the check of drainage is complete, open the check pin (CHK) and remount the tube cover.
(5) Checkpoint after installation
Fig. 1-130
Drainage check
Over 3-15/16”
(100 mm)
Plastic container
for water intake
Water (Approx. 0.3gal (1,200 cc))
Drain pan outlet
Indoor Unit control PC board
CHK
CAUTION
Be careful because the fan will start when you short the pin on the
indoor control board.
00_271485_Eng.indb 11
2015-5-20 12:50:50
Checkpoint
Checkpoint
Symptom
Check
Remark
1
Make sure whether indoor and outdoor units are
correctly installed.
Fall, vibration, noise
2
Make sure whether gas leakage is tested.
No cooling, no heating
3
Make sure whether insulation is completed.
(Refrigerant piping and drain piping)
Water leakage
4
Make sure whether drain water is running
smoothly.
Water leakage
5
Make sure whether the power voltage matches
the nameplate.
Inoperative, burnout
6
Make sure whether there is miswiring or incorrect
connection.
Inoperative, burnout
7
Make sure whether the ground construction is
completed.
Ground leakage
8
Make sure whether the wire gauge is followed by
the recommended specifications.
Inoperative, burnout
9
Make sure whether the air intake and air outlet
of the indoor and outdoor units are sealed by
obstacles.
No cooling, no heating
1
SM830203-04.indb 153
15/10/16 10:45:06
Содержание U-26PE1U6
Страница 8: ...vii MEMO...
Страница 76: ...1 68 1 Specifications 1 4 Dimensional Data Outdoor Unit U 26PE1U6 U 26PS1U6 U 36PE1U6 U 36PS1U6 1...
Страница 77: ...1 69 1 Specifications 1 4 Dimensional Data Outdoor Unit U 42PE1U6 U 42PS1U6 1...
Страница 218: ...2 12 MEMO...
Страница 219: ...3 1 3 2 Indoor Units 3 2 Outdoor Units 3 14 3 ELECTRICAL DATA 3 1 3...
Страница 220: ...3 2 3 Electrical data 3 1 Indoor Units Concealed Duct Type S 26PF2U6 S 36PF2U6 3...
Страница 221: ...3 3 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 222: ...3 4 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 223: ...3 5 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 224: ...3 6 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 225: ...3 7 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 226: ...3 8 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 227: ...3 9 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 228: ...3 10 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 230: ...3 12 3 Electrical data Wall Mounted Type S 26PK2U6 3...
Страница 232: ...3 14 3 Electrical data 3 2 Outdoor Units U 26PE1U6 3...
Страница 233: ...3 15 3 Electrical data U 26PE1U6 3...
Страница 234: ...3 16 3 Electrical data U 26PS1U6 3...
Страница 235: ...3 17 3 Electrical data U 26PS1U6 3...
Страница 236: ...3 18 3 Electrical data U 36PE1U6 3...
Страница 237: ...3 19 3 Electrical data U 36PE1U6 3...
Страница 238: ...3 20 3 Electrical data U 36PS1U6 3...
Страница 239: ...3 21 3 Electrical data U 36PS1U6 3...
Страница 240: ...3 22 3 Electrical data U 42PE1U6 3...
Страница 241: ...3 23 3 Electrical data U 42PE1U6 3...
Страница 242: ...3 24 3 Electrical data U 42PS1U6 3...
Страница 243: ...3 25 3 Electrical data U 42PS1U6 3...
Страница 244: ...MEMO 3 26...
Страница 284: ...5 24 MEMO...
Страница 297: ...201510...