1. Specifications
1-12. ELECTRICAL WIRING
General Precautions on Wiring
Recommended Wire Length and Wire Diameter for Power Supply System
You must follow LOCAL ELECTRICAL CODES for wiring.
Outdoor Unit
Type
Time delay fuse or
circuit capacity
U-26PE1U6
U-36PE1U6
U-42PE1U6
30 A
35 A
40 A
Type
Time delay fuse or
circuit capacity
U-26PS1U6
U-36PS1U6
U-42PS1U6
25 A
30 A
35 A
Indoor Unit
Type
Time delay fuse or
circuit capacity
U1, K1, T1, F1,
F2, U2, K2, T2
15 A
Control Wiring
(A) Inter-Unit Control Wiring
(B) Remote Control Wiring
(C) Control Wiring For Group Control
AWG #18
Use high voltage wire (300 V)
*1
AWG #18
*1
(0.75 mm
2
)
AWG #18
*1 -
(0.75 mm
2
)
Max. 650 - ft. (Total)
Max. 1,650 ft.
Max. 3,300 ft.
AWG=American Wire Gauge
*
With ring-type wire terminal
(1)
Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely
following the wiring diagram.
WARNING
(2) This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or
Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case of equipment
breakdown or insulation breakdown.
Earth Leakage Circuit Breaker (ELCB) must be incorporated in the fixed wiring in accordance with the
wiring regulations. The Earth Leakage Circuit Breaker (ELCB) must be an approved 15 A, having a
contact separation in all poles.
(3) To prevent possible hazards from insulation failure, the unit must be grounded.
(4) Each wiring connection must be done in accordance with the wiring system diagram. Wrong wiring may cause the
unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be very dangerous. The manufacturer will accept no responsibility
for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to locality. For field wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by electrical noise, care must be taken when wiring as follows:
The remote control wiring and the inter-unit control wiring should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between units and ground the shield on single side.
(9)
If the power supply cord of this appliance is damaged, it must be replaced by a repair shop designated by the
manufacturer, because special-purpose tools are required.
Control wiring
(A) Inter-unit
control wiring
(between outdoor
and indoor units)
(B) Remote control
wiring
(C) Control wiring
for group control
AWG #18
(0.75 mm
2
)
Use shielded wiring*
AWG #18
(0.75 mm
2
)
Use shielded wiring*
AWG #18
(0.75 mm
2
)
Use shielded wiring*
Max. 3,280 ft.
(Max. 1,000 m)
Max. 1,640 ft.
(Max. 500 m)
Max. 650 ft. (Total)
(Max. 200 m (Total))
1
SM830203-04.indb 97
15/10/16 10:44:49
Содержание U-26PE1U6
Страница 8: ...vii MEMO...
Страница 76: ...1 68 1 Specifications 1 4 Dimensional Data Outdoor Unit U 26PE1U6 U 26PS1U6 U 36PE1U6 U 36PS1U6 1...
Страница 77: ...1 69 1 Specifications 1 4 Dimensional Data Outdoor Unit U 42PE1U6 U 42PS1U6 1...
Страница 218: ...2 12 MEMO...
Страница 219: ...3 1 3 2 Indoor Units 3 2 Outdoor Units 3 14 3 ELECTRICAL DATA 3 1 3...
Страница 220: ...3 2 3 Electrical data 3 1 Indoor Units Concealed Duct Type S 26PF2U6 S 36PF2U6 3...
Страница 221: ...3 3 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 222: ...3 4 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 223: ...3 5 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 224: ...3 6 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 225: ...3 7 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 226: ...3 8 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 227: ...3 9 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 228: ...3 10 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 230: ...3 12 3 Electrical data Wall Mounted Type S 26PK2U6 3...
Страница 232: ...3 14 3 Electrical data 3 2 Outdoor Units U 26PE1U6 3...
Страница 233: ...3 15 3 Electrical data U 26PE1U6 3...
Страница 234: ...3 16 3 Electrical data U 26PS1U6 3...
Страница 235: ...3 17 3 Electrical data U 26PS1U6 3...
Страница 236: ...3 18 3 Electrical data U 36PE1U6 3...
Страница 237: ...3 19 3 Electrical data U 36PE1U6 3...
Страница 238: ...3 20 3 Electrical data U 36PS1U6 3...
Страница 239: ...3 21 3 Electrical data U 36PS1U6 3...
Страница 240: ...3 22 3 Electrical data U 42PE1U6 3...
Страница 241: ...3 23 3 Electrical data U 42PE1U6 3...
Страница 242: ...3 24 3 Electrical data U 42PS1U6 3...
Страница 243: ...3 25 3 Electrical data U 42PS1U6 3...
Страница 244: ...MEMO 3 26...
Страница 284: ...5 24 MEMO...
Страница 297: ...201510...