1-119
1-118
1. Specifications
CAUTION
To avoid gas from leaking
when removing the charge
hose, make sure the stem
of the gas tube is turned all
the way out (“BACK SEAT”)
position.
3. Charging Additional Refrigerant
Charging additional refrigerant (calculated from the
liquid tube length as shown in Section "1-13. Installation
Instructions, 1. Tubing Size, Table 1-4 Tubing Data for
Models", Amount of additional refrigerant charge) using
the liquid tube service valve. (Fig. 1-30)
Use a balance to measure the refrigerant accurately.
If the additional refrigerant charge amount cannot
be charged at once, charge the remaining
refrigerant in liquid form by using the gas tube
service valve with the system in Cooling mode at
the time of test run. (Fig. 1-31)
* If an additional refrigerant charge has been
performed, list the refrigerant tubing length and
amount of additional refrigerant charge on the
product label (inside the panel).
4. Finishing the Job
(1) With a hex wrench, turn the liquid tube service
valve stem counter-clockwise to fully open the
valve.
(2) Turn the gas tube service valve stem counter-clockwise
to fully open the valve.
(3) Loosen the charge hose connected to the gas
tube service port (5/16".) slightly to release the
pressure, then remove the hose.
(4) Replace the 5/16". fl are nut and its bonnet on the
gas tube service port and fasten the fl are nut
securely with an adjustable wrench or box wrench.
This process is very important to prevent gas from
leaking from the system.
(5) Replace the valve caps at both gas and liquid
service valves and fasten them securely.
Fig. 1-30
Fig. 1-31
Valve
Liquid
Manifold valve
Pressure
gauge
Lo
Hi
Outdoor unit
Liquid
tube
Gas
tube
Close
Close
Close
R410A
Outdoor unit
Liquid
tube
Gas
tube
Open
Open
Open
5. SELECTING THE INSTALLATION SITE
5-1. Indoor Unit
AVOID:
areas where leakage of flammable gas may be
expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near inverter lamps which may affect the
performance of the unit.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room
directly. This may cause “sweating” on the air dis-
charge ports, causing them to spray or drip.
locations where the remote controller will be splashed
with water or affected by dampness or humidity.
installing the remote controller behind curtains or
furniture.
locations where the receiver in the indoor unit is
exposed to the inverter lamp light. Faulty operation
of the unit occurs.
DO:
select an appropriate position from which every
corner of the room can be uniformly cooled.
select a location where the ceiling is strong enough
to support the weight of the unit.
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
If the indoor unit is installed on the ceiling where the
temperature or humidity inside is high (over 86°F(30°C)
/RH: 70%), add insulating material to the surface of the
unit to avoid dew condensation.
install the unit within the maximum elevation
difference above or below the outdoor unit and within
a total tubing length (L) from the outdoor unit as
detailed in the installation instructions packed with
the outdoor unit.
allow room for mounting the remote controller about
3 ft. off the floor, in an area that is not in direct
sunlight nor in the flow of cool air from the indoor
unit.
NOTE
Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 10 ft.
Indoor Unit
locations where high-frequency emissions are
generated.
Ceiling (Type T1)
The rear of the indoor unit can be
installed flush against the wall.
Min. 2 ft.
Air intake
Min. 10 inch
Ceiling
Wall
NOTE
Min. 10 inch
Side view
Front view
Type F2
Ceiling
Wall Mounted (Type K1)
Min.
6 inch
Min.
12 inch
Min.
6 inch
Low Silhouette Ducted (Type F1)
4-Way Cassette (Type U1)
10 in.
10 in.
10 in.
3 ft.
3 ft.
3 ft.
3 ft.
3 ft.
Min.8 ft.
Shows Low Silhouette Ducted Type only
Air
discharge
9-27/32”
(250 mm)
25-19/32”
(650 mm)
Wall Mounted (Type K2)
The air inlet and outlet of the indoor unit must be free of any
obstructions to allow air to spread throughout the room.
1. The indoor unit must be within a maintenance soace.
Front View
min. 3" (7.5 cm) min.
2"
(5
cm)
min.
2"
(5
cm)
1
SM830203-04.indb 118
15/10/16 10:44:55
Содержание U-26PE1U6
Страница 8: ...vii MEMO...
Страница 76: ...1 68 1 Specifications 1 4 Dimensional Data Outdoor Unit U 26PE1U6 U 26PS1U6 U 36PE1U6 U 36PS1U6 1...
Страница 77: ...1 69 1 Specifications 1 4 Dimensional Data Outdoor Unit U 42PE1U6 U 42PS1U6 1...
Страница 218: ...2 12 MEMO...
Страница 219: ...3 1 3 2 Indoor Units 3 2 Outdoor Units 3 14 3 ELECTRICAL DATA 3 1 3...
Страница 220: ...3 2 3 Electrical data 3 1 Indoor Units Concealed Duct Type S 26PF2U6 S 36PF2U6 3...
Страница 221: ...3 3 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 222: ...3 4 3 Electrical data 4 Way Cassette Type S 26PU1U6 S 36PU1U6 S 42PU1U6 3...
Страница 223: ...3 5 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 224: ...3 6 3 Electrical data Wall Mounted Type S 26PK1U6 3...
Страница 225: ...3 7 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 226: ...3 8 3 Electrical data Ceiling Type S 26PT1U6 S 36PT1U6 S 42PT1U6 3...
Страница 227: ...3 9 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 228: ...3 10 3 Electrical data Low Silhouette Ducted Type S 26PF1U6 S 36PF1U6 3...
Страница 230: ...3 12 3 Electrical data Wall Mounted Type S 26PK2U6 3...
Страница 232: ...3 14 3 Electrical data 3 2 Outdoor Units U 26PE1U6 3...
Страница 233: ...3 15 3 Electrical data U 26PE1U6 3...
Страница 234: ...3 16 3 Electrical data U 26PS1U6 3...
Страница 235: ...3 17 3 Electrical data U 26PS1U6 3...
Страница 236: ...3 18 3 Electrical data U 36PE1U6 3...
Страница 237: ...3 19 3 Electrical data U 36PE1U6 3...
Страница 238: ...3 20 3 Electrical data U 36PS1U6 3...
Страница 239: ...3 21 3 Electrical data U 36PS1U6 3...
Страница 240: ...3 22 3 Electrical data U 42PE1U6 3...
Страница 241: ...3 23 3 Electrical data U 42PE1U6 3...
Страница 242: ...3 24 3 Electrical data U 42PS1U6 3...
Страница 243: ...3 25 3 Electrical data U 42PS1U6 3...
Страница 244: ...MEMO 3 26...
Страница 284: ...5 24 MEMO...
Страница 297: ...201510...