Functions
© Panasonic Industrial Devices SUNX Co., Ltd. 2020
76
5-3-2 Muting mode
Select from parallel 4-sensor, cross 2-sensor, exit only, invalid when rising, and simultaneous
input.
5-3-3 Muting sensor input order (parallel 4-sensor, invalid when rising, exit only)
You can set the input order of muting inputs A and B for entry into the muting state.
●
A = B
Enters muting state regardless of which muting input is first
●
A→B
Enters muting state only when muting input A is first
●
B→A
Enters muting state only when muting input B is first
In a serial connection, the muting input order can be set separately for each light curtain.
5-3-4 Muting sensor output operation setting
You can select the output action of the muting sensor.
The factory setting is NO / NO (normally open / normally open).
●
NO/NO (Normally open / Normally open)
Muting sensor connected to muting input A
(ON when light not received, ON when approaching, ON when contact made)
Muting sensor connected to muting input B
(ON when light not received, ON when approaching, ON when contact made)
●
NO/NC (normally open / normally closed)
Muting sensor connected to muting input A
(ON when light not received, ON when approaching, ON when contact made)
Muting sensor connected to muting input B
(ON when light received, ON when away, ON when contact not made)
5-3-5 Muting input time limit value
●
When output operation of two muting sensors is NO / NO
The input times of inputs A and B are from a minimum of 0.03, and 0.1 to 59.9 sec., and a
maximum of 0.1 sec. to 60 sec. The value can be set in increments of 0.1 sec.
The factory settings are 0.03 sec. for the minimum value and 3 sec. for the maximum value.
To allow detection of a short-circuit failure between the two muting sensor outputs, the mini
-
mum value cannot be set to 0 sec.
●
When output operation of two muting sensors is NO / NC
The input times of inputs A and B are from a minimum of 0.03, and 0.1 to 59.9 sec., and a
maximum of 0.1 sec. to 60 sec. The value can be set in increments of 0.1 sec.
The factory settings are 0 sec. for the minimum value and 3 sec. for the maximum value.
Содержание SF4D-TM1
Страница 2: ... Panasonic Industrial Devices SUNX Co Ltd 2020 2 MEMO ...
Страница 26: ...Procedures for Operation Panasonic Industrial Devices SUNX Co Ltd 2020 26 MEMO ...
Страница 50: ...Software Tool Panasonic Industrial Devices SUNX Co Ltd 2020 50 MEMO ...
Страница 89: ... Panasonic Industrial Devices SUNX Co Ltd 2020 89 Chapter 6 Troubleshooting ...