Auxiliary output switching function (non-safety output)
The following outputs are switchable as the auxiliary output.
0. Negative logic of the control output (OSSD 1 / 2) (factory setting)
1. Positive logic of the control output (OSSD 1 / 2)
2. For emission: output ON, For non-emission: output OFF
3. For emission: output OFF, For non-emission: output ON
4. For unstable incident light: OFF (Note 1)
5. For unstable incident light: ON (Note 1)
6. For muting: ON
7. For muting: OFF
8. For light reception: ON, For light blocked: OFF (Note 2)
9. For light reception: OFF, For light blocked: ON (Note 2)
Notes: 1) The output cannot be used while the fix blanking function, floating blanking function or the muting func
-
tion is activated.
2) This device outputs the light received / blocked state under activating the auxiliary output switching
function using the handy controller irrespective of activating other functions: fixed blanking function,
floating blanking function and muting function.
<e.g.>
In case of activating the fixed blanking function, the control output (OSSD 1 / 2) becomes ON with the
shielded object existed in the setting range and other ranges are in light receiving status.
If the auxiliary output switching function activates in No. 8 output, this device becomes OFF because
the sensor itself detects the object.
●
Interlock setting changing function
It is selectable one interlock state among the following three interlock settings
•
Start / Restart interlock
The device goes into the interlock state after the power is turned ON, or when the light is
blocked.
The factory setting is start / restart interlock.
•
Start interlock
The device goes into the interlock state when the power supply is turned ON. Once this
interlock is reset, the device does not go into the interlock state.
•
Restart interlock
The device does not go into the interlock state when turning ON the power supply. Only
when the control output (OSSD 1 / 2) becomes ON and the light is blocked after the power
is turned ON and this device receives the light, the device goes into the interlock state.
●
External device monitor setting changing function
The setting of the external device monitor is changeable.
1. Allowable time for response time: 100 to 600ms (Unit: 10ms)
Factory setting is 300ms.
2. The external device monitor function can be selected to valid or invalid.
The factory setting is set to valid for the external device monitor function.