6-12
6
6
Never use the DN code unlisted in the following table.
(P) : Factory preset mode
DN
Item
Setting No.
05
Outdoor fan silent mode
1= Silent mode 1 (P)
2= Silent mode 2,,,,, 3= Silent mode 3
07
Capacity matching ignored
0= Invalid (P)
1= V alid
0C
Indoor unit drain pump forced operation
0= Invalid
1= stop for 2 hours and drive for 20 minutes constantly
2= stop for 20 minutes and drive for 20 minutes constantly
3= Drive constantly
4-6= delay drive when thermostat OFF
7= delay drive when thermostat OFF (P)
0D
M easures against smell when indoor unit cooling
thermostat OFF
0= Invalid (P)
1= M easures against smell
1A
Demand 1 current (% )
0= 0%
40= 40%
45= 45% ,,,,,
75= 75% (P) ,,,,,
130= 130%
-1= No control
1B
Demand 2 current (% )
0= 0%
40= 40%
45= 45% ,,,,,
50= 50% (P) ,,,,,
130= 130%
-1= No control
1D
Current control level
0= 40%
1= 45% ,,,,,
12= 100% ,,,,,
16= 120% ,,,,,
18= 130,,,,,
19 = -1(Invalid)(P)
2B
DP operation time for slime measures
20= 20 minutes
30= 30 minutes (P)
40= 40 minutes
50= 50 minutes
60= 60 minutes
(For details, see " 5. Outdoor Unit CCU Control (4)" )
80
Refrigerant Type
410= R410A(P), 22= R22, 407= R407C, 32= R32
81
Outdoor unit capacity
(Setting when the data is not stored in the EEPROM .
Do not change under normal conditions.)
0= Invalid
19 = 180 (Type 160) 20= 200 (Type 180)
21= 224 (Type 200) 22= 250 (Type 224)
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 12
17/12/27 14:23:24
Содержание S-160PE1R5A
Страница 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Страница 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Страница 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Страница 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...