1-38
1
1
Ensure to connect the electrical cable connections and clamp the wires securely to the terminal connections using cord clamps
so that no undue force is placed on the wires (power source cable, indoor/outdoor connection cables, earth lead wire).
Do not install a phase advance capacitor for power factor improvement. (It does not improve the power factor and will cause
abnormal overheating.)
Do not bind the excess cables together and place them inside this unit.
Protect the electrical cable with the protective bushing provided so that the cables do no get damaged on the knock hole or etched
portions. If there is space between the electrical cables and the protective bushing occurs, seal it accordingly.
Tie the cables with the provided binding strap so that they do not touch the compressor and the pipes.
When setting up the cables, inside of unit install properly so that the front panel will not lift up. Make sure that front pa nel mount
correctly.
Use a round type terminal with an insulation sleeve for connecting to the terminal block.
Use the appropriate screwdriver for tightening the terminal screws. Small sized
screwdriver damages the head of the screw and cannot tighten it properly.
There is risk of damaging the screw if the terminal screw is over
tightened. Tighten with the appropriate torque.
Seal wiring holes after wiring using included protection bush.
(other holes are for connecting conduit pipe)
Back direction
Sideways direction
Front direction
Screw diameter name
T
ightening torque N•m (k
g
f•m)
M4
1.6 ~ 2.0 (16.3 ~ 20.4)
M5
2.0 ~ 2.5 (20.4 ~ 25.5)
M6
4.0 ~ 4.5 (40.8 ~ 45.9)
Indoor/outdoor, 2-wire mode format, option connection
(demand, forced stop and subsystem connections only).
Indoor/outdoor
connection
(shielded cable)
Cord clamp
Earth terminal fi xing
for SG
(SG: Shows the earth
for the shielded cable)
Shielded cable option
control (when carrying out
demand, forced stop and
subsystem connection only).
Cord clamp
Demand
connection
terminal block
Power supply terminal block
Indoor/outdoor connection
terminal block
Subsystem connection
terminal block
Forced stop connection
terminal block
Earth lead wire
Earth terminal
Power line
Thermal insulating
piping materials
Please fi x all electrical lines
fi rmly with cord clamps.
Carry out wiring so that
wires are not stretched.
Insulate the terminal
portion (earth included)
with insulation sleeves.
Please tie the insulation piping
securely so that no electrical lines do
come into contact with the compressor
or exposed piping.
Standard accessories: tying bands (4)
Direction to pull out wires
WARNING
This air conditioner must be installed in accordance with national wiring regulations.
Cables connected to outdoor unit must be approved polychloroprene sheathed type 60245 IEC 57 or
H05RN-F/H07RN-F or heavier.
The units must be connected to the supply cables for fi xed wiring by qualifi ed technician.
Circuit breaker must be incorporated in the fixed wiring in accordance with the national wiring regulations.
The circuit breaker must be approved, suitable for the voltage and current ratings of equipment and
have a contact separation by 3mm in all poles.
When the supply cable is damaged, it must be replaced by qualified technician.
Be sure to install a current leakage breaker, main switch and fuse to the main power supply, otherwise
electric shocks may result.
Be sure to connect the unit to secure earth connection.
If the earthing work is not carried out properly, electric shocks may result.
Wiring shall be connected securely by using specified cables and fi x them securely so that external
force of the cables may not transfer to the terminal connection section.
Imperfect connection and fixing leads to fi re, etc.
The earth lead wire shall be longer than other lead wires as shown in the fi gure for
electrical safety in case it slips out of the cord from the anchorage.
Earth lead wire set up
Be sure to connect the wires correctly to terminal board with connecting the crimp
type ring terminal to the wires.
If connecting two separate wires to a single crimped terminal, place the two
crimped terminal wires together as shown in Fig. A. (If the arrangement shown
in Fig. B is used, poor contacts or contact damage may result.)
Fig. A (OK)
Fig. B (not OK)
Cord
clamp
SG
SG
How to connect wiring to the terminal
For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the insulation
to expose the stranded wiring about 10 mm and tightly twist
the wire ends.
Stranded wire
Ring
pressure
terminal
Strip 10 mm
(2)
Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using a ring connector fastener or pliers, securely clamp
each stripped wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and tighten
the removed terminal screw using a screwdriver.
Screw and
Special washer
Ring
pressure
terminal
Terminal board
Ring pressure
terminal
Screw
Special
washer
Wire
Wire
Wiring sample
Examples of shield wires
(1) Remove cable coat not to scratch braided shield.
(2) Unbraid the braided shield carefully and twist the
unbraided shield wires tightly together. Insulate the shield
wires by covering them with an insulation tube or wrapping
insulation tape around them.
Insulation tape
Shield mesh
(3) Remove coat of signal wire.
8 mm
Insulation tape
Shield mesh
(4) Attach ring pressure terminals to the signal wires and the
shield wires insulated in Step (2).
Earth wire f or power supply
The earth wire should be longer than the other lead wires for
electrical safety.
G round terminal fixing for
(Functional earthing)
Power
supply
Inter-unit
control wiring
Remote
control wiring
Clamper (supplied)
Earth wiring*
Power cable
* M ake the earth wiring
25 - 30 mm longer than
power cable.
< Ty pe E1>
< Ty pe E3 >
6P terminal board
Remote
control
wiring
Shielded
wire
ground
Power
supply
Earth
Inter-Unit
control
wiring
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 38
18/01/26 13:2 :27
Содержание S-160PE1R5A
Страница 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Страница 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Страница 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Страница 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...