7
7
Item code
Item
Description
10
Unit type
Set when the indoor unit EEPROM memory is replaced during servicing.
11
Indoor unit capacity
12
System (outdoor unit)
address
These are not set at the time of shipping from the factory.
These must be set after installation if automatic address setting is not
performed.
13
Indoor unit address
14
Group address
17
Cooling intake
temperature shift
Shifts the intake temperature during cooling and dry operation.
(Enabled only when the body thermostat is used.)
Increase this value when it is difficult to turn the thermostat ON.
18
Automatic stop time after
operation start
The time at which an indoor unit is automatically stopped after operation
starts can be set in increments of 5 minutes.
1b
Forced thermostat ON
time
Use this setting to change the time for forced operation at installation
or servicing from 5 minutes to 4 minutes.
1E
Temperature shift for
cooling / heating change
in “auto heat / cool” mode
“Auto heat / cool” selects the operating mode automatically based on
the difference between the room temperature and the temperature set
on the remote controller. This setting establishes a shift temperature for
the heating / cooling temperature setting relative to the remote controller
temperature setting.
Cooling temperature setting
Heating temperature setting
Remote controller temperature setting
Shift temperature
Shift temperature
7-6. Detailed Setting Items
Cooling temperature setting
Remote controller temperature setting
Heating temperature setting
Shift temperature
Shift temperature
7-10
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 10
18/01/2 17:42:11
Содержание S-160PE1R5A
Страница 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Страница 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Страница 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Страница 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...