1-44
1
1
Please secure necessary space to guarantee performance and service &
maintenance. For multiple installations, please secure enough space to enable
removal of side face screws between units. (unit: mm)
4. INSTALLATION SERVICE SPACE
Where there are obstacles at the intake
If upper part is open
1
Separate location
installation
2
Obstacles on both sides
More than 150
More than 250
More than
150
More than
200
3
Multiple units (more than 2 units)
Obstacles at the upper part (both sides open in separate location
installation)
Where there are obstacles at the discharge
If upper part is open
1
Separate location installation
More
than 500
2
Multiple units (more than 2 units)
More than 150
More than 150
More than 1500
More than 250
More than 250
More than 250
More than 150
More
than 200
More than 150
More than 30
0
Where there are obstacles on the intake and discharge
Upper part and both side faces are open
1
Separate location installation
More
than 150
More than 1000
2
Multiple units (more than 2 units)
More
than 300
More than 250
More than 250
More than 1500
Caution: Please ensure that the height of obstacles at either the front
or rear faces is less than 2m.
In the case of front and rear multiple units
Upper part and both side faces are open
(More
than
1500)
(More
than 300)
More than 2000
More than 300
Caution: Please ensure that the height of obstacles at either the front or
rear faces is 2m or below.
Caution: We recommend a maintenance space of more than
500mm for every 3 units in multiple units installation.
More than 500
1-39
1
5 . TRANSPORT AND INSTALL THE OUTDOOR UNIT
Transporting
1. Transport the outdoor unit in its original packaging as close as possible to the installation
location.
2. In the event that the unit needs to be lifted or suspended, use a rope or belt and use
cloth or wood as padding to avoid damaging the unit.
3. Use the side handles to carry the unit and be careful not to touch the
fi
n with your hand
or any objects.
Installation
1. Read the “ Select the outdoor unit installation location” thoroughly before installing the
outdoor unit.
2. When installing to a concrete or solid surface, use M10 or a W 3/8 bolts and nuts to
secure the unit. Ensure that it installed upright on a horizontal plane. (Use an anchor
bolt for the installation as shown in the diagram below.)
3. Avoid installing on the slanted roof.
4. In the even where the roof is at risk of receiving oscillations or vibrations, secure the unit
with a seismic isolating mount or vibration absorbing rubber.
5. The drain water will be discharged from the unit during heating or
defrosting operation mode.
Select an appropriate location with good drainage system. (In the
winter, there is risk of slipping due to freezing, and depending on the
installation set up there is risk of drain water running overhead.)
* In cold regions (where the outdoor temperature can drop to below
for 2 to 3 consecutive days), the drain water may freeze and
may prevent the fan from operating. For this case, do not use the
drain elbow.
More than 25mm
*1
More than
50mm
More than 40mm
B ase
Anchor bolt length
(Unit: mm)
(Anchor pitch)
20.5
412.5
17
355.5
19
5.5
159
230
200
160
350
660
159
(Anchor pitch)
Anchor bolt position
Drain hole ø 32
*1
・
Ordinarily, ensure a base height of 5 cm or more.
If a drain pipe is used, ensure a height of 15 cm or more at the
feet on both sides of the unit.
・
Precautions for Installation in H eavy Snow Areas.
The platform should be higher than the max. snow depth.
(In this case, leave clearance below the unit for the drain pipe,
and to prevent freezing of drainage water in cold-weather regions.
)
* When using a drain pipe, install the drain socket (field supply) onto the drain port.
Seal the other drain port with the rubber cap (field supply).
For details, refer to the instruction manual of the drain socket (field supply).
After completing the installation work of the drain socket, make sure that the
water does not leak from any part of connection.
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 44
18/01/26 13:2 :2
Содержание S-160PE1R5A
Страница 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Страница 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Страница 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Страница 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...