E15 A utomatic A ddress A larm (The total capacity of indoor units is too low.)
Error D etection M ethod
It is j udged an error the total capacity of indoor units replied by communication is lower than that of outdoor unit.
Connecting indoor unit
The total capacity of indoor units is lower than that of outdoor unit.
Some indoor unit(s) are connected but power is not turned on.
The CH K pin (CN062/CN071) and/or TEST pin (CN064) of the indoor unit is shorted when its power is turned on.
H igh voltage was applied (over AC200V ) in the indoor/outdoor operations line circuit.
1.
Is the indoor unit powered off?
1-1
Was the number of indoor units changed after auto address setting
finished?
3-1
Conduct checks prior to auto address setting.
3-2
3-2
3-1
Y es
No
Power on.
2-1
Y es
No
Was a high voltage (over AC200V ) applied in the indoor/outdoor
operations line circuit?
2-2
2
Is the indoor/outdoor control line opened or shorted?
2-1
Correct the wiring.
2-2
Y es
No
Indoor/
outdoor
control line
3 No. of
Indoor
Units
1 Power
Source
Error D iagnosis
2.
3-2
4-1
Y es
No
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board and see whether the E15 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
Replace wireless remote control parts including wiring.
4-3
4-4
Is the LED blinking on the indoor unit’ s control PC board?
4-5
Check all items under the section “Check Prior to Auto Address Setting”.
5-1
The nonvolatile memory (EEPROM ) on the indoor unit’ s control board is either not installed,
improperly installed or the nonvolatile memory is faulty. Correct this or after replacing the
nonvolatile memory, write model data to it in the remote control detailed settings mode.
4-6
Are the CH K pin and TEST pin on the indoor unit control board
short-circuited?
4-1
Is the wireless remote controller connected to on the indoor unit’ s
control PC board?
4-2
4-4
4-5
Y es
No
Remove the short.
4-2
Y es
No
4-3
4-5
Y es
No
4 Indoor
unit
control
PC board
5 Outdoor
unit control
PC board
4-6
5-1
Y es
No
For information on the remote control’ s detailed settings, refer to the Reference M aterials.
For information on the procedures for replacing the nonvolatile memory (EEPROM ) of the indoor unit, refer to the manual
that is packaged with the indoor unit service board.
I ndoor U nit Control PCB
C3 93 7 -8 40 -1Y : S-16 0 PE1R5 A
A CX A 7 3 -18 7 5 : S-18 0 PE3 R5 , S-20 0 PE3 R5 , S-225 PE3 R5
RC
EEPROM
POWER LED
EM G
OC
OPTION
EX CT
DISP
JP 001
CH K Pin
T10
FAN DRIV E
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 10
18/01/26 14:0 :17
Содержание S-160PE1R5A
Страница 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Страница 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Страница 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Страница 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...