![Panasonic S-160PE1R5A Скачать руководство пользователя страница 73](http://html.mh-extra.com/html/panasonic/s-160pe1r5a/s-160pe1r5a_technical-data-and-service-manual_269826073.webp)
1-65
1
1
9-2-10. O perating th e H igh -spec W
ired R emote
C ontroller (C Z -R TC 5A / C Z -R TC 5B )
H ow to set th e external static pressure
1. K eep pressing the
,
and
b uttons simultaneously f or 4 or more seconds.
The “Maintenance f unc” screen appears on the
LCD display.
Maintenance f unc
1. O utdoor unit error data
2. Serv ice contact
3. R C setting mode
4. Test run
Sel.
Page [
] Conf irm
20: 30 (THU )
2. Press the
or
b utton to see each
menu. If yo u w ish to see the next screen instantly,
press the
or
b utton.
Select “8. D etailed settings” on the LCD display
and press the
b utton.
Maintenance f unc
5. Sensor inf o.
6. Serv icing check
7. Simple settings
8. D etailed settings
Sel.
Page [
] Conf irm
20: 30 (THU )
The “D etailed settings” screen appears on the LCD
display.
Select the “U nit no. ” b y pressing the
or
b utton f or changes.
D etailed settings
U nit no.
Code no.
Set data
10
3- 1
0006
Sel.
N ext
20: 30 (THU )
3. Select the “Code no. ” b y pressing the
or
b utton.
Change the “Code no. ” to “5D ” b y pressing the
or
b utton (or ke eping it pressed).
D etailed settings
U nit no.
Code no.
Set data
1
0
0
0
1
-
3
Sel.
N ext
20: 30 (THU )
5D
STAR T
[
]
20: 30 (THU )
4.
Select the “Set data” b y pressing the
or
b utton.
Select one of the “Set data” among “0006”, “0003”
or “0001” according to the desired external static
pressure setting b y pressing the
or
b utton. (See Tab le 1- 8 and F ig. 1- 21. )
Then press the
b utton.
Tab le 1-8 S etting th e external static pressure
Indoor unit
Item code
180
5D
External static pressure of the rated
air ow v olume
150 Pa
0006
100 Pa
0003
60 Pa
200
180 Pa
120 Pa
75 Pa
224
200 Pa
130 Pa
75 Pa
0001
5. Select the “U nit no. ” b y pressing the
or
b utton and press the
b utton.
The “Exit detailed settings and restart? ” (D etailed
setting- end) screen appears on the LCD display.
Select “Y ES” and press the
b utton.
D etailed settings
U nit no.
Code no.
Set data
10
1- 1
0001
Sel.
N ext
20: 30 (THU )
Exit detailed settings
and restart?
N O
Y ES
SM830262-00_大洋州向け シングル天埋_TD&SM.indb 6
18/01/26 13:2 :36
Содержание S-160PE1R5A
Страница 8: ...vii MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 8 18 01 12 18 47 0 ...
Страница 98: ...1 90 MEMO SM830262 00_大洋州向け シングル天埋_TD SM indb 0 18 01 26 13 2 4 ...
Страница 196: ... MEMO 7 16 SM830262 00_大洋州向け シングル天埋_TD SM indb 16 18 01 2 17 42 12 ...
Страница 218: ...201801 SM830262 00_大洋州向け シングル天埋_TD SM indb 1 17 12 27 14 22 33 ...