3-6-3 Interlock connector connecting samples
Connect between INTERLOCK IN and INTERLOCK COM. with the non-voltage contact (relay output terminal etc.) of the
safety devices such as door, switch or safety PLC.
ワㄐㄕㄊㄆ
• INTERLOCK IN on the interlock connector are connected to the operating coil of the internal relay in the controller.
Connect INTERLOCK IN (No.3) and INTERLOCK COM. (No.1) with the non-voltage contact (dry contact) such as a relay
or a switch. Do not connect with the voltage contact such as a transistor.
Except LP-Sxxx-SF/LP-Sxxx-LS1 type
1. INTERLOCK COM.
3. INTERLOCK IN
1
2
3
INTERLOCK
To Emergency stop switch etc.
For LP-Sxxx-SF/LP-Sxxx-LS1 type
1. INTERLOCK 1 COM.
INTERLOCK 1
connector
2. FEEDBACK 1 OUT
3. INTERLOCK 1 IN
1
2
3
1. INTERLOCK 2 COM.
INTERLOCK 2
connector
2. FEEDBACK 2 OUT
3. INTERLOCK 2 IN
1
2
3
Safety PLC
N.O.
(Output from PLC)
Monitoring
(Input to PLC)
N.O.
(Output from PLC)
ンㄆㄇㄆㄓㄆㄏㄆ
• In the attached interlock connectors, INTERLOCK IN and INTERLOCK COM. are short-circuited at the delivery state.
• For LP-Sxxx-SF/LP-Sxxx-LS1 type, it is recommended to connect the interlock connectors to the external safety device
by using the relay output terminal of the safety relay unit or the safety PLC. Refer to “Construction of interlock system”
ME-LPS-SSM-8
Содержание LP-S Series
Страница 15: ...15 MEMO ME LPS SSM 8 ...
Страница 26: ...26 Chapter 1 Specification ME LPS SSM 8 ...
Страница 41: ...41 Chapter 2 Preparation ME LPS SSM 8 ...
Страница 78: ...Chapter 3 Connection for External Control ME LPS SSM 8 ...
Страница 126: ...Chapter 4 Maintenance ME LPS SSM 8 ...
Страница 148: ...Troubleshooting ME LPS SSM 8 ...
Страница 169: ...Index ME LPS SSM 8 ...
Страница 172: ...172 MEMO No 9000 0066 16V ME LPS SSM 8 ...
Страница 173: ...No 9000 0066 16V ...