11-10
11.3.3 Dealing with Operation Errors
<Procedure>
1. Check the location of the error.
Check the address where the error occurred, which is stored in DT90017 and DT90018, and make sure
the high-level instruction for that address is correct and appropriate.
2. Clear the error.
Use a programming tool to clear the error.
-
When using FPWIN GR, select "Online" -> "Status Display" in the menu bar.
Execute "Clear Error".
-
When using FPWIN Pro, select "Monitor" -> "PLC Status". Press the "Error Clear" button.
-
An error can be cleared by turning the power off and on in PROG. mode, however, the contents of the
operation memory except the hold type data will be cleared.
-
An error can also be cleared by executing a self-diagnostic error set instruction (F148).
-
If the mode selector is set to "RUN", RUN will resume as soon as the error is cleared. So if the cause of
the error is not removed, the error may seem not to be cleared.
11.3.4 Points to Check in Program
1. Check if an extraordinarily large value or negative value was stored in the index register.
<Example> When a data register is modified using an index register
In this case, index register modifies the address of data register DT0. However, it may exceed the
addressable range of the data register depending on the data in I0. If the value exceeds the range, an
operation error will occur. The same is true when the contents of I0 are a negative value.
2. Is there any data which cannot be converted using BCD
↔
BIN data conversion?
<Example> When BCD-to-BIN conversion is attempted
In this case, if DT0 contains a hexadecimal number with one of the digits A through F such as 12A4,
conversion will be impossible and an operation error will result.
<Example> When BIN-to-BCD conversion is attempted
In this case, if DT1 contains a negative value or a value greater than K9999, an operation error will occur.
3. Check if the devisor of a division instruction is “0”.
<Example>
In this case, if the content of DT100 is "0", an operation error will occur.
Содержание FP0R Series
Страница 1: ......
Страница 6: ...iv ...
Страница 14: ...xii ...
Страница 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 24: ...1 10 ...
Страница 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Страница 38: ...2 14 ...
Страница 39: ...Chapter 3 Expansion ...
Страница 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Страница 48: ...3 10 ...
Страница 49: ...Chapter 4 I O Allocation ...
Страница 53: ...Chapter 5 Installation and Wiring ...
Страница 73: ...Chapter 6 Preparation of USB Port ...
Страница 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Страница 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Страница 84: ...6 12 ...
Страница 85: ...Chapter 7 Communication ...
Страница 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Страница 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Страница 142: ...8 2 ...
Страница 199: ...Chapter 9 Security Functions ...
Страница 211: ...Chapter 10 Other Functions ...
Страница 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Страница 227: ...Chapter 12 Precautions During Programming ...
Страница 242: ...12 16 ...
Страница 243: ...Chapter 13 Specifications ...
Страница 254: ...13 12 ...
Страница 255: ...Chapter 14 Dimensions and Others ...
Страница 260: ...14 6 14 1 5 Power Supply Unit Unit mm 14 1 6 I O Link Unit Unit mm 14 1 7 When Using DIN Rail Unit mm ...
Страница 262: ...14 8 ...
Страница 263: ...Chapter 15 Appendix ...
Страница 344: ...15 82 15 7 ASCII Codes ...
Страница 346: ......
Страница 347: ......
Страница 348: ......