15-76
Error
code
Name
Opera-
tion
status
Description and steps to take
FP
-e
FP
0
FP
0R
FP
Σ
FP
-X
FP
2
FP2
SH
FP
10S
H
E46
Remote
I/O
commu-
nication
error
Selec-
table
S-LINK error Occurs only in FP0-SL1
When one of the S-LINK errors (ERR1, 3 or
4) has been detected, error code E46 (remote
I/O (S-LINK) communication error) is stored.
Selection of operation status using system
register27:
-to continue operation, set K1
-to stop operation, set K0
A
Selec-
table
MEWNET-F communication error
A communication abnormally was caused by
a transmission cable or during the power-
down of a slave station.
FP2, FP2SH, and FP10SH:
Check the contents of special data registers
DT90131 to DT90137 and locate the
abnormal slave station and recover the
communication condition.
FP3:
Check the contents of special data registers
DT9131 to DT9137 and locate the abnormal
slave station and recover the communication
condition.
Selection of operation status using system
register27:
-to continue operation, set K1
-to stop operation, set K0
A A A
E47
MEW-NET-
F
attribute
error
Selec-
table
In the unit on the slave station, an
abnormality such as:
-missing unit
-abnormal intelligent unit was detected.
FP2, FP2SH, and FP10SH:
Check the contents of special data registers
DT90131 to DT90137 and locate the
abnormal slave station and recover the slave
condition.
FP3:
Check the contents of special data registers
DT9131 to DT9137 and locate the abnormal
slave station and recover the slave condition.
Selection of operation status using system
register28:
-to continue operation, set 1
-to stop operation, set 0
A A A
E49
Expansion
unit power
supply
sequence
error
Stops
The power supply for the expansion unit was
turned on after the control unit.
Turn on the power supply for the expansion
unit at the same time or before the control
unit is turned on.
A
E50
Backup
battery
error
Conti-
nues
The voltage of the backup battery lowered or
the backup battery of control unit is not
installed.
⇒
Check the installation of the backup
battery and then replace battery if necessary.
By setting the system register 4, you can
disregard this self-diagnostic error.
A A A A A
Содержание FP0R Series
Страница 1: ......
Страница 6: ...iv ...
Страница 14: ...xii ...
Страница 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 24: ...1 10 ...
Страница 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Страница 38: ...2 14 ...
Страница 39: ...Chapter 3 Expansion ...
Страница 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Страница 48: ...3 10 ...
Страница 49: ...Chapter 4 I O Allocation ...
Страница 53: ...Chapter 5 Installation and Wiring ...
Страница 73: ...Chapter 6 Preparation of USB Port ...
Страница 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Страница 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Страница 84: ...6 12 ...
Страница 85: ...Chapter 7 Communication ...
Страница 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Страница 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Страница 142: ...8 2 ...
Страница 199: ...Chapter 9 Security Functions ...
Страница 211: ...Chapter 10 Other Functions ...
Страница 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Страница 227: ...Chapter 12 Precautions During Programming ...
Страница 242: ...12 16 ...
Страница 243: ...Chapter 13 Specifications ...
Страница 254: ...13 12 ...
Страница 255: ...Chapter 14 Dimensions and Others ...
Страница 260: ...14 6 14 1 5 Power Supply Unit Unit mm 14 1 6 I O Link Unit Unit mm 14 1 7 When Using DIN Rail Unit mm ...
Страница 262: ...14 8 ...
Страница 263: ...Chapter 15 Appendix ...
Страница 344: ...15 82 15 7 ASCII Codes ...
Страница 346: ......
Страница 347: ......
Страница 348: ......