7-14
7.4.5 1:N Communication (MEWTOCOL Slave Function)
A computer and PLCs are connected through a commercially available RS232C-RS485 converter, and
the respective computer and PLCs are wired using an RS485 cable with crossover wiring.
The computer and the PLC communicate via commands and responses: The computer sends a
command specifying the unit number, and the PLC with that unit number sends a response back to the
computer.
Note) LINEEYE CO., LTD SI-35 is recommended to be used as a converter. For the RS232C-type
COM port, a RS232C-RS485 conversion adapter is also required on the PLC side.
Setting of unit numbers
By default, the unit number for each communication port is set to 1 in the system register settings.
There is no need to change this for 1:1 communication, but if 1:N communication is used to connect
multiple PLCs to the transmission line (e.g. in a C-NET), the unit number must be specified so that the
destination of the command can be identified.
The unit number is specified by using the system register.
Setting system registers
No.
Name
Set Value
No. 410
Unit number
1 to 99 (Set the desired unit number)
(With a C-NET adapter, a maximum of 32 units
(stations) can be specified.)
No. 412
Communication mode
Computer link
No. 413
Communication format
Char. bit: ……
Parity: …..
Stop bit: …………
Terminator: ……..
Header: …………
7 bits/8 bits
None/Odd/Even
1 bit/2 bit
CR
STX not exist
No. 415
Baud rate
Note2)
2400 to 115200 bps
Note1) The communication format and baud rate should be set to match the connected computer.
Note2) The baud rates of 300, 600 and 1200 bps can be specified by the SYS1 instruction.
For using the RS485 type, make the same setting as that of the baud rate switches (19200 or 115200
bps).
Содержание FP0R Series
Страница 1: ......
Страница 6: ...iv ...
Страница 14: ...xii ...
Страница 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 24: ...1 10 ...
Страница 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Страница 38: ...2 14 ...
Страница 39: ...Chapter 3 Expansion ...
Страница 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Страница 48: ...3 10 ...
Страница 49: ...Chapter 4 I O Allocation ...
Страница 53: ...Chapter 5 Installation and Wiring ...
Страница 73: ...Chapter 6 Preparation of USB Port ...
Страница 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Страница 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Страница 84: ...6 12 ...
Страница 85: ...Chapter 7 Communication ...
Страница 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Страница 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Страница 142: ...8 2 ...
Страница 199: ...Chapter 9 Security Functions ...
Страница 211: ...Chapter 10 Other Functions ...
Страница 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Страница 227: ...Chapter 12 Precautions During Programming ...
Страница 242: ...12 16 ...
Страница 243: ...Chapter 13 Specifications ...
Страница 254: ...13 12 ...
Страница 255: ...Chapter 14 Dimensions and Others ...
Страница 260: ...14 6 14 1 5 Power Supply Unit Unit mm 14 1 6 I O Link Unit Unit mm 14 1 7 When Using DIN Rail Unit mm ...
Страница 262: ...14 8 ...
Страница 263: ...Chapter 15 Appendix ...
Страница 344: ...15 82 15 7 ASCII Codes ...
Страница 346: ......
Страница 347: ......
Страница 348: ......