-Self-diagnostic Error
This error occurs when the control unit (CPU unit) self-diagnostic function detects the occurrence of an
abnormality in the system. The self-diagnostic function monitors the memory abnormal detection, I/O
abnormal detection, and other devices.
When a self-diagnostic error occurs
- The ERROR turns on or flashes.
- The operation of the control unit (CPU unit) might stop depending on the content of error and the
system register setting.
- The error codes will be stored in the special data register DT9000(DT90000).
- In the case of operation error, the error address will be stored in the DT9017(DT90017) and
DT9018(DT90018).
Clearing the self-diagnostic error
At the “STATUS DISPLAY”, execute the “error clear”. Error codes 43 and higher can be cleared.
-You can use the initialize/test switch to clear an error. However, this will also clear the contents of
operation memory.
-Errors can also be cleared by turning off and on the power while in the PROG. mode.
However, the contents of operation memory, not stored with the hold type data, will also be cleared.
-The error can also be cleared depending on the self-diagnostic error set instruction F148(ERR).
Steps to take for self-diagnostic error
The steps to be taken will differ depending on the error contents. For more details, use the error code
obtained above and consult the table of self-diagnostic error codes.
MEWTOCOL-COM Transmission Errors
These are error codes from a PC or other computer device that occur during an abnormal response
when communicating with a PLC using MEWTOCOL-COM.
Содержание FP0R Series
Страница 1: ......
Страница 6: ...iv ...
Страница 14: ...xii ...
Страница 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 24: ...1 10 ...
Страница 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Страница 38: ...2 14 ...
Страница 39: ...Chapter 3 Expansion ...
Страница 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Страница 48: ...3 10 ...
Страница 49: ...Chapter 4 I O Allocation ...
Страница 53: ...Chapter 5 Installation and Wiring ...
Страница 73: ...Chapter 6 Preparation of USB Port ...
Страница 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Страница 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Страница 84: ...6 12 ...
Страница 85: ...Chapter 7 Communication ...
Страница 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Страница 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Страница 142: ...8 2 ...
Страница 199: ...Chapter 9 Security Functions ...
Страница 211: ...Chapter 10 Other Functions ...
Страница 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Страница 227: ...Chapter 12 Precautions During Programming ...
Страница 242: ...12 16 ...
Страница 243: ...Chapter 13 Specifications ...
Страница 254: ...13 12 ...
Страница 255: ...Chapter 14 Dimensions and Others ...
Страница 260: ...14 6 14 1 5 Power Supply Unit Unit mm 14 1 6 I O Link Unit Unit mm 14 1 7 When Using DIN Rail Unit mm ...
Страница 262: ...14 8 ...
Страница 263: ...Chapter 15 Appendix ...
Страница 344: ...15 82 15 7 ASCII Codes ...
Страница 346: ......
Страница 347: ......
Страница 348: ......