8-42
8.4.12 Precautions When Changing Speed (Common to F171 and F172)
Precautions during programming
-
To change the speed, specify the execution condition of instruction to be always executed.
-
Using the type 0 of trapezoidal control instruction (F171) enables to perform the
acceleration/deceleration control up to the target value. Using the type 1 of trapezoidal control
instruction (F171) enables to perform the acceleration/deceleration control up to the maximum speed
(50 kHz).
-
The speed cannot be changed during the deceleration requested by the deceleration stop and during
the deceleration to stop at the target position.
-
Acceleration cannot be performed from that position when the elapsed value goes beyond the
acceleration forbidden area starting position. The acceleration forbidden area starting position can be
monitored by the special data registers shown in the table below.
-
The speed cannot be changed to a value below the deceleration minimum speed. If a value below the
deceleration minimum speed is specified, the speed will be corrected. The deceleration minimum
speed can be monitored by the special data registers shown in the table below.
Pulse output control area
Channel No.
Deceleration minimum speed area
Acceleration forbidden area
starting position area
CH0
DT90407
DT90408 to DT90409
CH1
DT90417
DT90418 to DT90419
CH2
DT90427
DT90428 to DT90429
CH3
DT90437
DT90438 to DT90439
Содержание FP0R Series
Страница 1: ......
Страница 6: ...iv ...
Страница 14: ...xii ...
Страница 15: ...Chapter 1 Functions and Restrictions of the Unit ...
Страница 24: ...1 10 ...
Страница 25: ...Chapter 2 Specifications and Functions of Control Unit ...
Страница 38: ...2 14 ...
Страница 39: ...Chapter 3 Expansion ...
Страница 45: ...3 7 3 4 Terminal layout diagram Model No Terminal layout diagrams E8RS E8RM E16RS E16RM E8YRS ...
Страница 48: ...3 10 ...
Страница 49: ...Chapter 4 I O Allocation ...
Страница 53: ...Chapter 5 Installation and Wiring ...
Страница 73: ...Chapter 6 Preparation of USB Port ...
Страница 77: ...6 5 5 Click Finish on the following screen to be displayed ...
Страница 79: ...6 7 4 Double click on FP0R 5 Click Update Driver ...
Страница 84: ...6 12 ...
Страница 85: ...Chapter 7 Communication ...
Страница 139: ...7 55 Sample program For Type II Use a program as below to directly specify a MODBUS address ...
Страница 141: ...Chapter 8 High speed Counter Pulse Output and PWM Output Functions ...
Страница 142: ...8 2 ...
Страница 199: ...Chapter 9 Security Functions ...
Страница 211: ...Chapter 10 Other Functions ...
Страница 217: ...Chapter 11 Self Diagnostic and Troubleshooting ...
Страница 227: ...Chapter 12 Precautions During Programming ...
Страница 242: ...12 16 ...
Страница 243: ...Chapter 13 Specifications ...
Страница 254: ...13 12 ...
Страница 255: ...Chapter 14 Dimensions and Others ...
Страница 260: ...14 6 14 1 5 Power Supply Unit Unit mm 14 1 6 I O Link Unit Unit mm 14 1 7 When Using DIN Rail Unit mm ...
Страница 262: ...14 8 ...
Страница 263: ...Chapter 15 Appendix ...
Страница 344: ...15 82 15 7 ASCII Codes ...
Страница 346: ......
Страница 347: ......
Страница 348: ......