Table 6: Modbus address list – Boolean status and coil registers
Register tag name
Register
address
Number of
registers
Description
Register type
HEARTBEAT
0
1
Heartbeat (from flare.IQ)
Status register
COMM_FAIL
1
1
Modbus comm failed (timeout)
Status register
RESERVED_02
2
1
Reserved, returns 0
Status register
FUEL_DEMAND_BQ
3
1
Fuel demand exceeds capacity
Status register
STEAM_DEMAND_BQ
4
1
Steam demand exceeds capacity
Status register
AIR_DEMAND_BQ
5
1
Air demand exceeds capacity
Status register
AR_BQ
6
1
Argon content value bad
Status register
CO2_BQ
7
1
Carbon dioxide content value bad
Status register
CO_BQ
8
1
Carbon monoxide content value bad
Status register
H2_BQ
9
1
Hydrogen content value bad
Status register
N2_BQ
10
1
Nitrogen content value bad
Status register
O2_BQ
11
1
Oxygen content value bad
Status register
H2O_BQ
12
1
Water content value bad
Status register
MW_INPUT_BQ
13
1
Mol weight from GC/MS value bad
Status register
NHVVG_INPUT_BQ
14
1
NHV (vent gas) from GC/MS value bad
Status register
RESERVED_15
15
1
Reserved, returns 0
Status register
RESERVED_16
16
1
Reserved, returns 0
Status register
QFUEL_BQ
17
1
Fuel gas flow measurement bad
Status register
RESERVED_18
18
1
Reserved, returns 0
Status register
QFLARE_BQ
19
1
Flare flow measurement bad
Status register
TFLARE_BQ
20
1
Flare temperature measurement bad
Status register
PFLARE_BQ
21
1
Flare pressure measurement bad
Status register
CFLARE_BQ
22
1
Flare sound speed measurement bad
Status register
RESERVED_23
23
1
Reserved, returns 0
Status register
QSTEAM_BQ
24
1
Steam flow measurement bad
Status register
TSTEAM_BQ
25
1
Steam temperature measurement bad
Status register
RESERVED_26
26
1
Reserved, returns 0
Status register
QAIR_BQ
27
1
Air flow measurement bad
Status register
TAIR_BQ
28
1
Air temperature measurement bad
Status register
PAIR_BQ
29
1
Air pressure measurement bad
Status register
RESERVED_30
30
1
Reserved, returns 0
Status register
CALC_SS_BQ
31
1
Calculated sound speed invalid
Status register
RESERVED_32
32
1
Reserved, returns 0
Status register
RESERVED_33
33
1
Reserved, returns 0
Status register
34
Содержание flare.IQ Generation 2
Страница 1: ...flare IQ Generation 2 Operation and maintenance manual...
Страница 2: ...2...
Страница 3: ...flare IQ Generation 2 Operation and maintenance manual 910 350 rev A June 2020 3...
Страница 4: ...no content intended for this page 4...
Страница 38: ...Figure 30 System wiring diagram 38...
Страница 48: ...48...
Страница 49: ...no content intended for this page 49...