Table 12: Modbus address list for flare.IQ Gen 1 legacy customers (analog outputs for flare control)
Register tag name
Register
address
Number of
registers
Description
Scaling
factor
QFUEL_DEMAND
0
1
Fuel gas demand, SCFH
*10
QSTEAM_DEMAND
1
1
Steam demand (PPH)
*10
NHVCZ_ACTUAL
2
1
Net heating value in the combustion zone
calculated, BTU/SCF
1
VTIP_ACTUAL
3
1
Flare tip velocity calculated, ft/s
/100
VTIP_MAX
4
1
Flare tip velocity maximum, ft/s
/100
MW_CALC
5
1
Molecular weight calculated, g/mol
/100
NHVCZ_MEASURED
6
1
Net heating value in the combustion zone
derived from GC/calorimeter, BTU/SCF
1
NHVCZ_CURRENT
7
1
Net heating value in the combustion zone
derived from mol weight, BTU/SCF
1
NHVCZ_MEASURED_TC
8
1
Net heating value in the combustion zone at
current fuel and steam, BTU/SCF
1
NHVCZ_UNCORRECTED_TC
9
1
NHVcz uncorrected for H2 at current fuel and
steam, BTU/SCF
1
NHVCZ_UNCORRECTED_ACTUAL
10
1
NHVcz uncorrected for H2 at demand fuel and
steam, BTU/SCF
1
NHVCZDIL_ACTUAL
11
1
NHV dilution parameter calculated
(Air Assist only), BTU/SCF
/10
NHVCZDIL_MEASURED
12
1
NHV dilution parameter from GC/calorimeter
(air assist only), BTU/SCF
/10
NHVCZDIL_MEASURED_TC
13
1
NHV dilution from GC/calorimeter at
current conditions (air assist only), BTU/SCF
/10
CF_ASSIST
14
1
Air/steam correction factor as a function of
mol weight, unitless
1
QAIR_DEMAND
15
1
Air demand (CFM)
*10
SPARE_AR_3
16
1
Spare
SPARE_AR_4
17
1
Spare
SPARE_AR_5
18
1
Spare
SPARE_AR_6
19
1
Spare
SPARE_AR_7
20
1
Spare
SPARE_AR_8
21
1
Spare
45
Содержание flare.IQ Generation 2
Страница 1: ...flare IQ Generation 2 Operation and maintenance manual...
Страница 2: ...2...
Страница 3: ...flare IQ Generation 2 Operation and maintenance manual 910 350 rev A June 2020 3...
Страница 4: ...no content intended for this page 4...
Страница 38: ...Figure 30 System wiring diagram 38...
Страница 48: ...48...
Страница 49: ...no content intended for this page 49...