1.3 Equipment overview
The system hardware includes two 19” rack mounting
sheet metal modules that house compact fanless digital
processing units (DPU), redundant power supplies, a pair of
ethernet switches and other power distribution equipment
and cables. The top power distribution and networking
module is shared with up to six DPU modules installed in the
bottom module (figure 2). A single DPU module is configured
to control a single flare stack while a second DPU module
loaded with identical firmware and settings provided for
redundancy. However, a single DPU is adequate for digital
verification of a single flare flow meter given the relatively
low frequency of this procedure. For example, if a customer
site has two flare stacks that need to be controlled, one
power distribution and network (top) module and a bottom
module with four (4) DPUs installed would be required. The
power distribution and networking module weighs 8.65 lbs.
(3.92 kg) and the bottom DPU module with the maximum
number (6) of DPU’s installed weighs 8.55 lbs. (3.88 kg).
4U high power
distribution and
network module (top).
One power distribution
and network module
can support up to
six DPUs
3U high DPU module
(bottom)
Figure 2: Front view of rack mounted control equipment
WARNING!
A disconnect power switch is required
to be installed within 30” (2.5 feet) of the
rack-mounted panels.
WARNING!
To ensure the safe operation of this unit,
you must install and operate the flare.IQ as
described in this user’s manual. In addition,
be sure to follow all applicable safety codes
and regulations for installing electrical
equipment in your area.
10
Содержание flare.IQ Generation 2
Страница 1: ...flare IQ Generation 2 Operation and maintenance manual...
Страница 2: ...2...
Страница 3: ...flare IQ Generation 2 Operation and maintenance manual 910 350 rev A June 2020 3...
Страница 4: ...no content intended for this page 4...
Страница 38: ...Figure 30 System wiring diagram 38...
Страница 48: ...48...
Страница 49: ...no content intended for this page 49...