9
GHI
Type infrared ceramic heaters
User’s Manual
Attachment of flexible gas pipe has to be directly to the outside threaded gas connection of appliance located on the back side of it.
Works to be performed during gas connection
• Gas pipes clearing
The thorough clearing of gas-supply system is very important before attachment of appliance.
• Gas leakage checking
After installation of appliance make sure about leak-proof mounting of connections. This action must be fulfilled after every
dismounting and assembling!
•
SOLELY INTERIOR installation is possible.
•
The installation must comply with the valid standards.
•
For the sake of appropriate effeciency the position and the high of installation has to be carefully defined.
•
The appliance has to be placed in that way that its every part be accessible.
Appliance installation
ATTENTION! The appliance can only be operated by gas defined on the data board of appliance !
The nominal values of gas-supply pressure:
• in case of natural gas: 25 mbar ( min. 20 mbar – max. 60 mbar )
• in case of Propan gas: 50 mbar
The allowed maximum pressure of gas-supply: 60 mbar!
ATTENTION! If the pressure of gas-supply is higher than 60 mbar in that case the using of pressure
regulator is indispensible becuse the max. allowed pressure of double-closed solenoid valve is:
Pmax = 60mbar
Gas connection
The pressure regulator can be installed before each appliance or centrally namely one piece into the gas-supply pipe. In case of unique
solution - namely there is pres-sure regulator before each appliance – before every pressure regulator, in case of centrally mounted
pressure regulator before pressure regulator and each appliance
MUST BE INSTALLED GAS FILTER
to be able to avoid the blocking
of appliance’s gas magnetic valves, which can be caused by possible contamination settled in the supply pipes.( despite blowing out of
pipes it can be present)
VIGYÁZAT
!
VESZÉLY
!
VIGYÁZAT
!
ÁRAM
ELLÁTÁS
The pressure regulator can be installed before each appliance or centrally namely one piece into the gas-supply pipe. In case of unique
solution - namely there is pres-sure regulator before each appliance – before every pressure regulator, in case of centrally mounted
pressure regulator before pressure regulator and each appliance
MUST BE INSTALLED GAS FILTER
to be able to avoid the blocking
of appliance’s gas magnetic valves, which can be caused by possible contamination settled in the supply pipes.( despite blowing out of
pipes it can be present)
The connection to the gas-supply pipe must be from above or side (Pic.5) because in case of bottom connection the possible contami
-
nations settled on the pipe can influence the proper operation of equipment.
PROPER CONNECTION
IMPROPER CONNECTION
4. picture: Connection to the gas supply
Gázsz
ű
r
ő
Tömít
ő
gy
ű
r
ű
Gáz elzáró-szerelvény
Flexibilis gáztöml
ő
5. picture: Attachment with flexible pipe
(option, it can be purchased at the appliance manufacturer)
Gas filter
Gasket ring
Gas shut off valve
Flexible pipe