Type infrared ceramic heaters
User’s Manual
7.
Troubleshooting
Malfunctions
Symptoms
Possible causes
Corrective actions
Ignition and flame
sensing system
Ceramic Surface
There is no spark be-
tween electrodes of the
igniter
•
The electrodes of igniter is polluted
•
Electrical connection between igniter and
automation is broken
•
Spark interval is too large
•
Automatic control went wrong
•
The ceramic on ignition elektrode is broken,
•
Clean electrodes
•
Check electrical connection
between ingnition module and auto
•
Check spark interval
•
Please change the ignition and
ionization electrode
•
Replace automatic control
Ignition cycle is fin
-
ished normally
Appliance does not oper-
ate after the first ignition
cycle
•
The gas supply valve is turned off
•
Air is not removed sufficiently from
aspipe
• Nozzle pressure is not suitable
•
Turn on the gas supply valve
•
Remove the air from the pipe
•
Check the input and output pres-
sure on the solenoid valve
Ignition cycle is fin
-
ished normally
Appliance does not oper-
ate after the first ignition
cycle
•
Solenoid valve went wrong
• Uncertain connection between ignition
module and automatic control
• Nozzle pressure is not suitable
•
Replace the solenoid valve
•
Replace the differential switch
•
Check the input and output pres-
sure on the solenoid valve
The ceramic burner ig-
nites but stops soon
•
The phase and null are replaced
• Nozzle pressure is not suitable
•
The ceramic plates are contamined
•
The Ignition electrode is touching the
catalitic grid
•
Check the wires connection points
•
Check the input and output pres-
sure on the solenoid valve
•
Please clean all the cearamic pla-
tes. (compressed air is required)
•
Please remove, and keep some
distance from the catalitic grid (at least
2 mm)
The unit is working, but
the efficiency, as also
the temeperature of the
ceramic plates are lower
as the normal opeatin
condition
• Nozzle pressure is not suitable
•
The ceramic plates are contamined
•
Please clean all the cearamic plates.
(compressed air is required)
•
Check the input and output pres-
sure on the solenoid valve
Appliance operates but
the combustion is une-
ven and noisier than it
should be
• Nozzle pressure is not suitable
•
Check the input and output pres-
sure on the solenoid valve
By using a manual ignition
unit. after the ignition pro-
cess the thermocouple do
not stays open.
•
Faulty thermocouple
•
The thermocouple is contamined
•
Please change the thermocouple
•
The disamble and cleaning of the
thermocouple