13
GHI
Type infrared ceramic heaters
User’s Manual
Attention! Before any maintanance and service process of the appliance, it needs to be disconected
from the power supply and unplug the gas supply!
11.picture: Assemblage of the gas magnetic valve
direction of gas flow
Test system start-up and check the regular operation of device.
Checking the regular operation
After starting the appliance, let it run for several minutes and close the gas tap. The appliance stops functioning and then after at least 8
seconds reinserts the gas tap, the appliance restarts after the safety time has elapsed.
To ensure the long life of the GHI type infrared devices, it is recommended that the device is examined and maintained at least once a
year by a specialist or a specialist.
Check at the beginning of season
Maintenances
The first adjustment of the appliance must be carried out only from a well educated technician!
To fulfil this requirement the easi
-
est way if You order this procedure by the producer or by the nearest distributor. If You decide to order the first adjustment procedure by
the producer or by the distributor please feel free to contact our colleagues!
ATTENTION! At the first start need to check the outlet gas pressure!
Value of the outlet gas pressure:
Automatic appliances
• Natural gas and S-gas: 16 mbar
• Propane gas and PB gas: 45 mbar
Manual appliances:
• Natural gas and S-gas: 20 mbar
• Propane gas and PB gas: 45 mbar
General informations
The flame control is a self controlling device and it controls only the Burner which it will intervenes and it is not sensitive against other
environmental effects such as external heat, light, and so on...
inlet pressure
outlet pressure