Type infrared ceramic heaters
User’s Manual
9.picture: Installation of the GHI heaters and safety distances
Tilting angle of heater should be adjusted according to values given in referring plan. Most frequent values: 45° and 60°, which
mean the pitch of ceramic surface to the floor. At hanging from the ceiling, at least 30° minimum tilting must be ensured! The
minimal tilting what is allowed at GHI-23 and GHI-36 appliances is 45°!
Adjustable device holder gaps
min. 500mm
min.800mm
Suspension
Warning! DO NOT ALLOWED to install he GHI appliances into “A” and “B” specified fire-protection
class! The installation must comply with the valid standards!
Disregard of these instructions can result in death, injury or property damage!
Infrared heaters are to be mounted on welded or assembled consoles built in the side wall of the hall to be heated, eventually on the
ceiling, and secured with M8 bolts.
The heaters do not possess integral combustion product exhausting system, so must be ventilate the room. Min. 16 max. 24 m³/h air
exchange is necessary at every built-in/kW.
Ventilation
The distance of any inflammable materials from the heater must be chosen with ensure, that the surface temperature of these materials
could NOT reach 50 °C. In cases when it is not possible, a fireproof heat protection plate must be used.
Protective distances to be kept considering flammable materials
Warning! The installation of appliance must be only executed by qualified service or specialist author
-
ized by retailer.
The 2 years guarantee of appliance can be ensured only in this case.
6.
Appliance operation
Before putting operation of appliance the leak-proof/pressure test of gas sup-ply system must be fulfilled. Clean duct system of gas supply
from any contamination.
• Check the presence and cleanness of gas filter located before the appliance
• Check the presence and suitability of pressure regulator located centrally or before every appliance.( the pressure regulator is
needed if the gas supply pressure is higher than 60 mbar,in this way the capacity of pressure regulator can be max. 60 mbar)
• Make sure of protective ground of appliance.
• Check the proper electrical connection of temperature regulator.
• Open the gas supply valve.
• Check the gas pressure on the inlet side of (magnetic) solenoid valve.(the maximum allowed pressure is 60 mbar).
• Connect the mains voltage to the appliance by temperature regulator or central stage main-switch.
• Check the outlet pressure of solenoid valve, whether the set up pressure –nozzle pressure – is suitable for the type of gas.
Adjustment of gas pressure happens only in that case, when device does not operate satisfactorily within the value adjusted by the
manufacturer. Device is factory-adjusted, but because of the different positioning circumstances it is practical to adjust it after the on-the-
spot installation. The characteristic heat technical data is only expected from well-adjusted devices. A qualified technician should make
adjustment of heating device.
45°