Only certified venting systems or components may be installed with this fireplace.
Only the following vent terminals should be used for the Tofino i40.
Min. Vent Height
10’ (3m)
Manufacturer
Model
Model #
Venting length
Duravent
High wind
terminal
DVA-CL33 10’ to 28’
Duravent
High wind
terminal
DVA-CL34 10’ to 40’
ICC
Co linear terminal
CT3
10’ to 28’
ICC
Co linear terminal
CT4
10’ to 40’
Combustion
Air Intake
Exhaust
Vent
13
100000300 051119-48
i40 TOFINO
1. Measure chimney height, cut flex liner (min.10’) as required. Mark
one pipe at both ends to identify combustion air intake pipe from flue
outlet pipe.
2. Attach marked flex liner pipe to the intake side of vent terminal. Seal
and secure with sealant and screws provided. Attach the other pipe
to the outlet side of vent terminal. Seal and secure with sealant and
screws provided.
3. Insert both flex liners from top of the chimney, down through the
damper opening.
4. Attach and seal according to vent terminal manufacturers’ instructions
5. For larger chimneys, a flashing may be cut and fitted to suit. Caulk the
flashing in place to seal any gaps.