When the Craftsman Arched Front is installed on a FP 30 AR Series B Fireplace, the chase requires
16 sq.in.
[100cm2]
of chase inlet air. This air helps support the fireplace’s convection airflow and is separate from the
Combustion Intake air. The duct doesn’t have to be round or a single inlet. The requirement is that the total
inlet area must be equal to 16sq.in. or greater.
This air must enter the chase no higher than 12” [305mm] from the bottom of the fireplace. And can be placed
on the front (off to the side of the unit "Figure 44: FP30 Crafstman Installed." or on the sides or back of the
chase if it protrudes into the room. Air can be drawn from under the chase, if that space is sealed within the
house envelope. The air must come from inside the house, preferably the room the fireplace is installed in.
Dimensions to note when installing the non-combustible wall board
A
Non-combustible wall board and all decorative facing materials.
B
Minimum height from base of the fireplace covered by non-combustible wall
board
84” (2.135m)
C
Minimum width of non-combustible wall board covering front of unit.
60”(1.525m
D
Supplied steel stud wall section.
E
Combustible stud framing.
F
Chase air intake - locate on front between unit and chase side wall if the chase
front is flush with wall. ("Chase Air Inlets" on page 29 for distance from
opening).
Min. 16 sq.” (100 cm2)
F
Chase air intake - Can be located on the side, back or underneath the chase,
as long as that inlet is drawing air from inside the room.
Min. 16 sq.” (100 cm2)
E
D
A
B
C
F
Figure 44: FP30 Crafstman Installed.
Chase Inlet
40
100000811_200418-48
FP30 Series B