Minimum Framing Dimensions
The top front framing must be built
as shown, (Figure 10) with no wood
framing directly in front of the chimney
system
WARNING: The fireplace must not be
in contact with any insulation or loose
filling material. If you are insulating the
chase, cover the insulation with drywall
or non-combustible panels. Maintain all
proper clearances.
WARNING: Drywall materials are
considered combustible and theIr
thickness must be accounted for in
your framing dimensions.
The open volume inside the chase is
required for heat management. Do Not
build a recess, shelves or cupboards
in the area above this fireplace. Do
not build or place anything inside this
Minimum chase area.
Do Not insulate the front portion of the
chase above the unit.
The Steel Stud framing kit must be
used for installing this Fireplace
.
24”
610mm
73”
1.85m
1”(25mm)
DISTANCE FROM BACK OF UNIT
TO REAR WALL
35 5/8
”
905mm
56 1/2”
1.44m
25 1/4”
641mm
5 3/8”
137mm
73”
1.85m
56 1/2”
1.44m
16” [406mm]
103
1/4
”
2.62m
8” [203mm]
NOTE: The framing dimensions shown are the
minimum to combustibeles. Framing dimensions
will need to be enlarged accordingly to accept
drywall/wallboard if used inside enclosure.
Figure 9: FP30 Framing dimensions.
24”
[610mm]
56 1/2”
[1.435m]
63 5/8”
[1.62m]
7’
[2.134m]
Minimum,
Inside enclosure,
from base of the
unit.
18”
[455mm]
18”
[455mm]
Figure 10: FP30 framing enclosure.
17
100000811_200418-48
FP30 Series B