This Accessory Face can only be used on an FP 30 ARCH Series B Wood Fireplace.
This manual covers the clearances, assembly and installation specific to this optional Craftsman surround.
Installation of the fireplace into the chase and venting is covered in this Series B Owners Manual. and must
be followed for safe operation. This section supperceeds any clearances or requirements for chase air inlet
written in the FP30 AR series B main manual.
This Installation requires the use of a chase air inlet to supplement the air required for both natural and forced
convection through the unit.
The Top Brow Mount and Side Brackets must be in place before placing the non-combustible board on the
front of the fireplace.
IMPORTANT
Craftsman Surround Installation
A Minimum distance from top of the Arch to 4” [100mm] deep combustible mantel
14” (355mm)
B Minimum distance from base of the fireplace to 4” [100mm] deep combustible mantel 51 3/4” (1.315m)
C Minimum distance from top of the Arch to 12” [305mm] deep combustible mantel
22” (560mm)
D Minimum distance from base of the fireplace to 12” [305mm] deep combustible
mantel
59 3/4” (1.52m)
E Minimum distance from the sides of the fireplace door to Mantle Pillars/Legs (max. 3
1/2” [90mm]deep)
10” (255mm)
F Minimum distance between the Mantle Pillars/Legs (max. 3 1/2” [90mm]deep)
47 1/2” (1.205m
G Minimum distance from a Side Wall to the side of the fireplace door
29” (735mm)
H Minimum distance from the base of the fireplace to the ceiling
84” (2.135m)
** Minimum depth of (UL1618 Class 1) non-combustible Ember Protection from the front
of the fireplace
18” (460mm)
L Minimum width of (UL1618 Class 1) Ember Protection: In Canada
:In U.S.A.
58” (1.47m)
39”
Craftsman Fireplace Clearances (Figure 38)
Clearances
B
B
C
A
B
I
F
G
E
H
D
Figure 38: FP30.Body B Craftsman Surround - Clearance.
36
100000811_200418-48
FP30 Series B