Handbook
November 2011
/
59-UMC0071
/
Issue
01
Mercury
iTC
Page 121
THEORY OF CONTROL LOOPS
Original Instructions
A PID controller can be made to operate in On-Off mode by setting the proportional
band (P) parameter to zero.
12.2.3
Proportional control
A proportional control system allows the heater power to be continuously varied. This
overcomes the oscillation problem produced by an on-off control system. The heater
voltage at any instant is proportional to the error between the measured temperature
and the setpoint. If the sample temperature drops, the heater voltage increases to
compensate.
A proportional control system reaches equilibrium below the setpoint. This is because
the heater output at the setpoint (when the error is zero) is zero. Thus a negative error is
required to produce enough heater output to balance the heat-losses to the
surroundings.
The temperature error can be reduced by making the proportional control apply to only a
part of the temperature range of the system. Below this proportional band the heater
voltage is at its maximum value. However reducing the proportional band too far
produces temperature oscillations (in the limit, a proportional band of zero degrees
produces on-off control).
Figure 12-2 Proportional band control
A PID controller can be made to operate in proportional-band mode by setting the
proportional band (P) parameter to a positive temperature value.