![OutBack Power SmartRE 2500 Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/outback-power/smartre-2500/smartre-2500_installation-manual_1660807050.webp)
Specifications
48
900-0033-01-00 Rev A
the current flows (hours). This applies equally to the amount you take out of a battery (discharging) or
the amount you put into it (charging).
Discharge Rate
Deep cycle batteries express the amp-hour rating as "at the x-hour rate". This is an average rate of
current flow that would take x number of hours to discharge the batteries. Common amp-hour figures
are at the 6-hour rate, the 20-hour rate, and the 100-hour rate. A battery is classified as having fewer
amp hours if it is discharged at a faster rate, such as the 6-hour rate. There is an inevitable amount of
heat associated with the flow of current through a battery. The higher the amount of current, the
greater the amount of heat generated. The heat is energy which is no longer available to the battery
to power loads. Hence, at a higher discharge rate, the batteries effectively have fewer amp-hours
available. Generally, the 20-hour rate is the most common one.
Estimating Amp Hours
To estimate the battery bank requirements, first calculate the amount of power to be drawn from the
batteries during the period of autonomy. This power draw is then translated into amp hours (Ah)—the
unit of measure to express deep-cycle battery capacity.
Amp-hours are calculated multiplying the current drawn by the load by the length of time it will
operate.
Watts to Amps
To calculate amps when the power consumption is expressed in watts, use the following equation:
A = W/V
where W = watts and V = volts DC
For example:
A 100 watt light bulb will draw approximately 8.33 amps
8.33 = 100 /12
If the light runs for three hours it will consume (8.33 x 3) or 25 Ah of power.
IMPORTANT:
For these calculations, do not use the AC amp rating of a device. AC amps are
measured on a different scale and will not give correct results.
Time and Power
The length of time a load is operated will affect the power draw. In some cases, an appliance which
draws a large wattage may not consume as many amp-hours as a load drawing fewer watts but
running for a longer period of time.
Amps to Watts
All electrical appliances have labels which state their energy consumption. Look for an amps rating on
motors and a watts rating on other appliances.
If the label plate has expressed power consumption in AC amps, multiply by volts for the watts
required (watts = volts x amps).
Содержание SmartRE 2500
Страница 1: ...Installation Manual...
Страница 19: ...Planning 900 0033 01 00 Rev A 17 Dimensions Figure 6 Enclosure Dimensions...
Страница 28: ...Installation 26 900 0033 01 00 Rev A Figure 14 Correct Placement for Vertical Installations...
Страница 29: ...Installation 900 0033 01 00 Rev A 27 Removing the Interior Cover Figure 15 Removing the Interior Cover...
Страница 54: ......
Страница 56: ...Wiring Configurations 54 900 0033 01 00 Rev A This page intentionally left blank...
Страница 64: ...Wiring Configurations 62 900 0033 01 00 Rev A This page intentionally left blank...