Specifications
900-0033-01-00 Rev A
47
Renewable Energy Input & Storage
PV Sizing
Single charge control systems can support photovoltaic arrays with the following specifications. Dual
charge controller systems can handle 2 arrays with the following specifications.
Maximum Array Size
¾
4,000 W
STC
¾
145 Vdc (150 V
OC
including local temperature correction factor per NEC 690.7)
¾
64 A I
SC
maximum PV array current per NEC 690.8
A PV string-sizing tool is available on the following website link:
¾
http://outbackpower.com/resources/string_sizing_tool/
Battery Bank Sizing
In general, the size of the loads (watts) and the required backup period (hours) will determine best size
(amp-hour capacity) for the battery bank.
Running Time and Size
The battery bank’s size determines the length of time the inverter can supply AC output power. The
larger the bank, the longer the inverter can run and the longer the recharge time.
Depth-of-Discharge
The battery bank should be designed so the batteries do not discharge more than 50-60% of their
capacity on a regular basis. Discharging up to 80% is acceptable on a limited basis, such as a
prolonged utility outage. Totally discharging a battery can reduce its effective life or permanently
damage it. Consult the battery manufacturer for specific depth-of-discharge recommendations.
Days of Autonomy
Days of autonomy may vary depending upon the availability of the charging source(s), the critical
nature of the load and other factors. If the system is to be powered by renewable energy sources such
as solar, determine the appropriate number of days of autonomy by allowing for cloudy weather as
well as other seasonal variations in available energy.
Back up power systems which use utility power for recharging should use the estimated number of
days of maximum power outage for determining days of autonomy.
Amp-Hour Requirements
Amp-hour requirements will vary with each installation depending on the loads that are connected
and the desired amount of time for those loads to be supported in the event that utility power is
unavailable
Amp-hour Capacity
Deep cycle batteries have a capacity measured in amp-hours. Amp-hours are a measure of current
flow over time. An amp-hour figure is derived by multiplying current (amperes) by the amount of time
Содержание SmartRE 2500
Страница 1: ...Installation Manual...
Страница 19: ...Planning 900 0033 01 00 Rev A 17 Dimensions Figure 6 Enclosure Dimensions...
Страница 28: ...Installation 26 900 0033 01 00 Rev A Figure 14 Correct Placement for Vertical Installations...
Страница 29: ...Installation 900 0033 01 00 Rev A 27 Removing the Interior Cover Figure 15 Removing the Interior Cover...
Страница 54: ......
Страница 56: ...Wiring Configurations 54 900 0033 01 00 Rev A This page intentionally left blank...
Страница 64: ...Wiring Configurations 62 900 0033 01 00 Rev A This page intentionally left blank...